Matters ▸ Attachment
225 CMR 23 MA Commercial Front end amended Clean 12-8-22 — File 22-0084
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
1 | P a g e
Massachusetts Stretch Code and Specialized Code for Commercial buildings
(Note: please see 225 CMR 22.00 for low-rise Residential construction)
The Massachusetts Stretch energy code (Stretch Code) first became available for municipal
adoption in 2009 as Appendix 110.aa and then 115.aa as part of the building code in 780 CMR.
In 2021 the Massachusetts legislature passed new legislation moving authority for updates to
the Stretch Code to the Department of Energy Resources and 225 CMR.
This code takes effect on July 1, 2023 and is designed to align with the forthcoming MA 10th
edition building code promulgated under 780 CMR. Building permit applications for projects
received on or after July 1, 2023 in Stretch Code communities shall comply with this code.
As with the 10th edition building code, this energy code is based on modified versions of the
2021 code books as published by the International Code Council (ICC). Specifically, the 2021
International Energy Conservation Code (IECC 2021) as amended.
This section (225 CMR 23) covers all buildings except for low-rise residential buildings which are
covered by 225 CMR 22. 225 CMR 22 and 23 in combination form the Stretch Code – and must
be adopted together and not in part.
Municipalities may also elect to adopt the combination of Appendix RC of 225 CMR 22 (Low rise
residential) and Appendix CC of 225 CMR 23 (all other buildings) which together form the
Municipal Opt-in Specialized code (Specialized Code).
For communities that have adopted the Stretch Code, the following 225 CMR 23 amendments
to the IECC 2021 apply together with 225 CMR 22 for low-rise residential buildings.
For communities that adopt the Specialized Code, the following 225 CMR 23 amendments apply
in combination with Appendix CC, along with 225 CMR 22 and Appendix RC for low-rise
residential buildings.
In both the Stretch Code and the Specialized Code these amendments to the IECC 2021 replace
Chapter 13 – Energy Efficiency of 780 CMR in the Base energy code.
Please remember that the Massachusetts amendments posted online are unofficial versions
that are made available for convenience. Official versions of the Massachusetts amendments
may be purchased from the State House Bookstore at www.sec.state.ma.us/spr/ and the IECC
2021 can be purchased from the ICC at www.iccsafe.org
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
2 | P a g e
225 CMR 23: MASSACHUSETTS FRONT-END AMENDMENTS TO THE INTERNATIONAL ENERGY
CONSERVATION CODE 2021
MASSACHUSETTS STRETCH ENERGY CODE – 2023 Commercial
amendments to IECC2021
CHAPTER 1 [CE] SCOPE AND ADMINISTRATION
SECTION C103 CONSTRUCTION DOCUMENTS
C103.2 Insert after Subsection C103.2(13) the following:
14. Solar Ready roof zone in accordance with Appendix CB, or Potential Solar Zone Area
in accordance with Appendix CC.
15. EV Ready Spaces locations in accordance with Section C405.13
16. For buildings using the Relative Performance Pathway (C407.2) because average
ventilation at full occupancy is greater than 0.5 cfm/sf, submit mechanical equipment
schedules for all new and/or existing air handling equipment designed to supply any
quantity of outdoor air to the space, and an airflow riser diagram encompassing the
complete project boundary. Mechanical equipment schedules shall clearly indicate the total
design outdoor airflow for each unit. The air riser diagram shall include all supply, exhaust,
and return air systems serving the space. The air riser diagram shall also include a summary
of the total outdoor air supplied, the total gross square footage served by the ventilation
system, and the overall flow rate per area in cfm/sf.
17. For mixed fuel building following Appendix CC, construction documents showing
electric HVAC retrofit design prepared by the HVAC engineer. The contract documents
shall show future replacement of combustion equipment based HVAC system with an
equivalent all electric system. Contract documents shall show combustion equipment to be
replaced, future electric equipment, supporting electric, structural, and architectural
infrastructure to be installed during building construction, and space allotments for future
equipment.
C103.2.2 Add the following Subsection:
C103.2.2 COMcheck submittal. The construction documents submitted with the
application for permit shall be accompanied by completed COMcheck Envelope, Lighting
and Mechanical Compliance Certificates, and a Plan Review Inspection Checklist for the
purposes of demonstrating compliance with the energy provisions of 225 CMR 23.00:
Stretch Energy Code.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
3 | P a g e
Exception: Projects documenting compliance following Section C407.2 (ASHRAE 90.1
Appendix G) shall follow applicable reporting requirements.
CHAPTER 2 [CE] DEFINITIONS
SECTION C202 GENERAL DEFINITIONS
C202 Add the following definitions:
ALL-ELECTRIC BUILDING. A building with no on-site combustion equipment for fossil fuel
use or capacity for including fossil fuel use in space heating, water heating, cooking, or drying
appliances.
AUTOMATIC LOAD MANAGEMENT SYSTEMS (ALMS). A control system that allows
multiple connected electric vehicle supply equipment (EVSE) to share a circuit or panel and
automatically manage power at each charger, reducing the total connected electrical capacity of
all EVSE.
CLASS 3 EXHAUST. Exhaust meeting the definition of Class 3 air in ASHRAE/ASHE
Standard 62.1-2019, including air with significant contaminant concentration, significant
sensory-irritation intensity, or offensive odor. The Class 3 Exhaust system must be capable of
reducing exhaust and makeup airflow rates to 50% of the zone design values or the minimum
required to maintain pressurization relationship requirements.
CLASS 4 EXHAUST. Exhaust meeting the definition of Class 4 air in ASHRAE/ASHE
Standard 62.1-2019, including laboratory fume hood exhaust, exhaust where energy recovery is
not allowed by ASHRAE/ASHE Standard 170 for use in energy recovery systems with leakage
potential, and systems exhausting toxic, flammable, paint or corrosive fumes or dust. The Class
4 Exhaust system must be capable of reducing exhaust and makeup airflow rates to 50% of the
zone design values or the minimum required to maintain pressurization relationship
requirements. Excludes exempt exhaust.
CLEAN BIOMASS HEATING SYSTEM. Wood-pellet fired central boilers and furnaces with
less than 3 million Btu/hour rated heat input, where the equipment has a thermal efficiency rating
of 85% (higher heating value) or greater; and a particulate matter emissions rating of no more
than 0.08 lb. PM2.5/MMBtu heat output. Or wood chip fired central boilers and furnaces with less
than 3 million Btu/hour rated heat input, where the equipment has a thermal efficiency rating of
80% or greater and a particulate matter emissions rating of no more than 0.10 lb. PM2.5/MMBtu
heat output.
COMBUSTION EQUIPMENT. Any equipment or appliance used for space heating, service
water heating, cooking, clothes drying and/or lighting that can use fuel gas, fuel oil or solid fuel
and that is not a clean biomass heating system.
DEDICATED OUTSIDE AIR SYSTEM (DOAS): A ventilation system that supplies 100
percent outdoor air primarily for the purpose of ventilation and that is a separate system from the
zone space-conditioning system.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
4 | P a g e
ELECTRIC VEHICLE. An automotive-type vehicle for on-road use, such as passenger
automobiles, buses, trucks, vans, neighborhood electric vehicles, electric motorcycles, and the like,
primarily powered by an electric motor that draws current from a rechargeable storage battery, fuel
cell, photovoltaic array, or other source of electric current.
Informational note: defined as in 527 CMR 12 section 625.2.
ELECTRIC VEHICLE SUPPLY EQUIPMENT (EVSE): The conductors, including the
ungrounded, grounded, and equipment grounding conductors, and the electric vehicle connectors,
attachment plugs, and all other fittings, devices, power outlets, or apparatus installed specifically
for the purpose of transferring energy between the premises wiring and the electric vehicle.
Informational note: defined as in 527 CMR 12 section 625.2.
ELECTRIC VEHICLE READY PARKING SPACE (“EV READY SPACE”): A designated
parking space which is provided with wiring and electrical service sufficient to provide 240 volt
AC Level 2 or equivalent EV charging, as defined by Standard SAE J1772 for EVSE servicing
light duty electric vehicles.
ENTHALPY RECOVERY RATIO. The ratio of change in enthalpy of the entering supply
airflow and the leaving supply airflow to the difference in enthalpy between the entering supply
airflow and the entering exhaust airflow, with no adjustment to account for that portion of the
psychrometric change in the leaving supply airflow that is the result of leakage of entering
exhaust airflow rather than exchange of heat or moisture between the airstreams.
EXEMPT EXHAUST. Exhaust for which energy recovery systems are prohibited by the
applicable International Mechanical Code.
EXHAUST SOURCE HEAT PUMP. A type of electric heat pump that utilizes ventilation
exhaust air as the thermal energy source.
FUEL GAS. A natural gas, manufactured gas, liquified petroleum gas or a mixture of these.
Informational note: Definition of fuel gas is mirrored from 2021 IMC to be useful in defining
combustion equipment. It typically refers to natural gas and propane.
FUEL OIL. Kerosene or any hydrocarbon oil having a flash point not less than 100°F (38°C).
Informational note: Definition of fuel oil is mirrored from 2021 IMC to be useful in defining
combustion equipment. It typically refers to heating oil products
GLAZED WALL SYSTEM. System consisting of any combination of both vision glass and/or
spandrel sections to create an above-grade wall that is designed to separate the exterior and
interior environments. These systems include, but are not limited to, curtain walls, window
walls, and storefront windows.
MIXED-FUEL BUILDING. A building that contains combustion equipment or includes piping
for such equipment.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
5 | P a g e
OTHER EXHAUST. Any exhaust that does not fall under the categories of Exempt Exhaust,
Class 4 Exhaust, or Class 3 Exhaust.
SENSIBLE ENERGY RECOVERY RATIO. The change in the dry-bulb temperature of the
outdoor air supply divided by the difference between the outdoor air and entering exhaust air
dry-bulb temperatures, expressed as a percentage.
SPANDREL SECTION. The opaque portion of a glazed wall system typically used to conceal
or obscure features of the building structure or used for visual effect. A spandrel section may
consist of, but is not limited to, an exterior exposed cladding layer (glazing or opaque material)
with an interior insulated panel.
TENANT SPACE FIT OUT ZONE. Portion of a building in which only the envelope is
completed, and the mechanical, lighting, and other interior systems are either incomplete or
partially complete at the time of building permitting. Mechanical, lighting, and other interior
systems may be completed under either the same building permit or a different building permit
from the host building.
THERMAL BRIDGE: Part of the building envelope where otherwise uniform thermal
resistance is changed by full or partial penetration of the thermal insulation by materials with
higher thermal conductivities and/or where the interior and exterior areas of the envelope are
different, such as, but not limited to, parapets and corners.
CLEAR FIELD: A thermal bridge that is uniformly distributed throughout an assembly
such that accounting for the thermal bridge individually is impractical for whole-building
calculations.
LINEAR: A thermal bridge that is continuous in one direction of the exterior envelope.
POINT A thermal bridge that is discrete and countable on an individual basis for whole-
building calculations.
CHAPTER 3 [CE] GENERAL REQUIREMENTS
SECTION C301 CLIMATE ZONES
C301 Replace Section C301 as follows:
C301.1 General. Massachusetts is in climate zone 5A
CHAPTER 4 [CE] COMMERCIAL ENERGY EFFICIENCY
SECTION C401 – GENERAL
C401.2 Replace Section C401.2 as follows:
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
6 | P a g e
C401.2 Application. Commercial buildings shall comply with either Section C401.2.1 or
C401.2.2. When constructed for the first time, all requirements imposed on the building housing
a tenant space fit out zone shall also apply to the tenant space fit out zone. Commercial buildings
containing multiple use type classifications (mixed-use buildings) shall comply with C401.2.4
C401.2.1 Prescriptive and Performance Compliance. Commercial buildings shall
comply with one of the following:
1.
Prescriptive Compliance: This pathway may only be used for any nonresidential
building, or portions thereof when following C401.2.4, up to 20,000-sf. The
Prescriptive Compliance pathway requires compliance with Sections C401.3,
C402 through C406, and Section C408.
2.
Targeted Performance Compliance: This pathway shall be used for dormitory,
fire station, library, office, school, police station, post office, and town hall
buildings, or portions thereof when following C401.2.4, over 20,000-sf which
have average ventilation at full occupancy of 0.5 cfm/sf or less. This pathway can
also be used for any building of any size. After 1 July 2024, this pathway shall be
used for residential buildings, or portions thereof when following C401.2.4, over
12,000-sf, or the building may comply with Section C401.2.2. The Targeted
Performance Compliance pathway requires compliance with Section C401.3,
Sections C402 through C406, Section C407.1, Section 408, and select sections of
ANSI/ASHRAE/IESNA 90.1-2019 Appendix G as described in Section 407.1.
3.
Relative Performance Compliance: This pathway may be used by buildings not
required to use Option 2. The Relative Performance Compliance pathway
requires that the Proposed building complies with Sections C401.3, C402.1.5,
C402.2.8, C402.3, C402.4, C402.5, C402.6, C402.7, C403.5, C403.7, C405,
C406, C407.2, C408, and ANSI/ASHRAE/IESNA 90.1-2019 using the Appendix
G compliance pathway as modified in Section C407.2.
Exception: Additions, alterations, repairs and changes of occupancy to existing buildings
complying with Chapter 5. This exception does not include tenant space fit out zones
when constructed for the first time.
C401.2.2 Certified Performance Standard Compliance. Commercial buildings or
portions thereof when following C401.2.4 shall comply with one of the following
certified performance standards:
1.
Passive House Compliance: This pathway can be used for any building of any
size. The Passive House Compliance pathway requires compliance with Sections
C401.3, C402.3, C405, C407.3 and C408.
2.
HERS Compliance: This pathway can be used for any Group R building with
multiple individual dwelling units. The HERS pathway requires compliance with
Section C401.3, C402.3, C405, C407.4 and C408.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
7 | P a g e
C401.2.4 Add Section C401.2.4 Mixed Use Buildings
C401.2.4 Mixed Use Buildings. Where different building use types within a new
building require different Section C401.2 Compliance Pathways, each use type shall
separately and individually show compliance with C401.2.1 or C401.2.2 for that
respective use type.
C401.4 Add Section C401.4 as follows:
C401.4 Building electrification. Building projects which utilize Section C407.2.1 shall
conform with C401.4.1. Building projects which utilize Section C402.1.5.2 shall conform with
C401.4.2 except for buildings using the Relative Performance pathway because average
ventilation at full occupancy is greater than 0.5 cfm/sf which shall comply with C401.4.1 rather
than C401.4.2. Building projects which utilize Section CC104.1, Part 1 shall conform with
C401.4.3.
C401.4.1 Partial Space Heating Electrification. Electric air source, exhaust source, or
ground source heat pump systems shall supply 25% of the building’s peak space heating
and ventilation air heating load at the ASHRAE 99.6% winter climatic design condition.
Heat pumps used for space and ventilation air heating shall comply with C401.4.4.
C401.4.1.1 Heat Pump Primary Operation. Heat pump systems shall be
controlled to prioritize their primary operation, prior to operation of supplemental
fossil-fuel equipment, during non-emergency conditions.
C401.4.2 Full Space Heating Electrification. Electric air source, exhaust source, or
ground source heat pump systems shall supply 100% of the building’s peak space heating
and ventilation air heating load at the ASHRAE 99.6% winter climatic design condition.
No fossil fuel heating equipment shall be used for space heating or ventilation air heating.
Heat pumps used for space and ventilation air heating shall comply with C401.4.4.
C401.4.3 Full Space and Water Heating Electrification. Electric air source, exhaust
source, or ground source heat pump systems shall supply 100% of the building’s peak
space heating and ventilation air heating load at the ASHRAE 99.6% winter climatic
design condition. Electric air source, ground source, electric resistance, or solar thermal
systems shall supply 100% of the building’s service water.
No fossil fuel equipment shall be used for space heating, ventilation air heating, or
service water heating. Heat pumps used for space and ventilation air heating shall comply
with C401.4.4. Heat pump service water heating shall conform to the applicable
efficiencies in Section C404.2. Solar thermal service water shall have a solar fraction of
0.4 or larger.
C401.4.4 Heat Pump Requirements. Heat pumps used for space heating and ventilation
air heating shall comply with C401.4.4.1 through C401.4.4.3.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
8 | P a g e
C401.4.4.1 Equipment Efficiencies. Heat pump equipment shall conform to the
applicable efficiencies in Section C403.3.2.
C401.4.4.2 Multiple Systems. For buildings with multiple heat pump systems,
compliance shall be based on the combined capacity of all heat pump systems
serving the building. For purposes of this calculation, the heating capacity of a
heat pump system shall not exceed the heating load of that system and the portion
of the building served by that system.
C401.4.4.3 Exhaust Source Heat Pumps. For purposes of this calculation, the
capacity of exhaust source heat pumps shall only include the heating capacity that
exceeds the energy recovered by the minimum ventilation heat recovery required
by C403.7.4. In addition, for purposes of this calculation, the capacity of the
exhaust source heat pumps shall not exceed the heat pump capacity when the
exhaust airflow is at 50% of design airflow.
C402.1.3 Delete Subsection C402.1.3 and Table C402.1.3 and mark as Reserved.
C402.1.3 Reserved.
C402.1.5 Replace Section C402.1.5 with the following:
C402.1.5 Component Performance Alternative. Above grade wall and fenestration
values and areas determined in accordance with C402.1.5.1 or C402.1.5.2 shall be an
alternative to compliance with the above grade wall U- factors in Tables C402.1.4 and
vertical fenestration U- factors in Table C402.4 and the maximum allowable fenestration
areas in Section C402.4.1. Fenestration shall meet the applicable SHGC requirements of
Section C402.4.3. Buildings following ANSI/ASHRAE/IESNA 90.1-2019 Appendix G
shall comply with this section. Roofs, below grade walls, floors, slab-on-grade floors, and
opaque doors shall comply with the values in Table C402.1.4.
C402.1.5.1 Low Glazed Wall System Buildings. Buildings in which less than or
equal to 50% of the total, above-grade wall area of the building thermal envelope
is a glazed wall system shall comply with Equation 4-2a and vision glass used in
the glazed wall system shall have a maximum whole assembly U factor of U-0.25.
Area-weighted U proposed <= 0.1285
(Equation 4-2a)
where:
Area-weighted U proposed = U value for each distinct assembly type of the above
grade wall portion of the building thermal envelope weighted by
vertical area for each distinct assembly type.
C402.1.5.2 High Glazed Wall System Buildings. Buildings in which more than
50% of the total, above-grade wall area of the building thermal envelope is a
glazed wall system shall comply with Equation 4-2b and vision glass used in the
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
9 | P a g e
glazed wall system shall have a maximum whole assembly U factor of U-0.25 and
the building complies with Section C401.4.2.
Area-weighted U proposed <= 0.1600
(Equation 4-2b)
where:
Area-weighted U proposed = U value for each distinct assembly type of the above
grade wall portion of the building thermal envelope weighted by
vertical area for each distinct assembly type.
Exception:
Buildings using the Relative Performance pathway because average
ventilation at full occupancy is greater than 0.5 cfm/sf shall comply with
C401.4.1 rather than C401.4.2.
C402.2.4.1 Delete the exception in Subsection C402.2.4.1:
C402.2.8 Add Subsection C402.2.8 as follows:
C402.2.8 Fireplaces. New combustion fireplaces shall have tight-fitting flue dampers or
doors, and outdoor combustion air as required by the fireplace construction provisions of
MA Construction Codes, as applicable. Where using tight-fitting doors on factory-built
fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and
listed for the fireplace.
C402.3 Replace Section C402.3 with the following:
C402.3 Rooftop solar readiness (Mandatory).
Follow Appendix CB: Solar-ready zone – Commercial.
C402.4 Modify Vertical fenestration U-factors in TABLE C402.4 as follows:
CLIMATE ZONE 5 AND MARINE 4
Vertical fenestration U-factor
Fixed fenestration
0.30
Operable fenestration
0.32
Add Subsection C402.4.6:
C402.4.6 Fenestration Documentation. In accordance with Section 303.1.3 fenestration
performance shall be documented according to C402.4.6.1 or C402.4.6.2.
C402.4.6.1 Labeled Performance. The thermal transmittance of glazed
fenestration products within the scope of NFRC shall be indicated by labels
applied to the products at the manufacturing location or by a label certificate
produced by an NFRC Approved Calculation Entity.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
10 | P a g e
C402.4.6.2 Calculated Performance. Fenestration products outside the scope of
NFRC may demonstrate compliance by submitting a thermal simulation report
prepared by a registered design professional for each product as defined by NFRC
100. Thermal simulations shall be performed in accordance with the NFRC 100-
2020 simulation procedures at the size and configuration defined in NFRC 100
Table 4-3.
C402.5 Replace Section C402.5 with the following:
C402.5 Air leakage—thermal envelope. The building thermal envelope shall comply with
Sections C402.5.1 through Section C402.5.10.1.
C402.5.1 Replace Section C402.5.1 with the following and delete the exception:
C402.5.1 Air barriers. A continuous air barrier shall be provided throughout the building
thermal envelope. The continuous air barrier is permitted to be any combination of inside,
outside, or within the building thermal envelope. The air barrier shall comply with Sections
C402.5.1.1, and C402.5.1.2. The air leakage performance of the air barrier shall be verified
in accordance with Section C402.5.2.
C402.5.1.1 Replace Section C402.5.1.1 with the following:
C402.5.1.1 Air barrier design and documentation requirements. Design of the
continuous air barrier shall be documented in the following manner:
1.
Materials, assemblies, and systems comprising the continuous air barrier
and their position within each building thermal envelope assembly shall be
identified.
2.
Joints, interconnections, and penetrations of the continuous air barrier
materials, assemblies, and systems shall be detailed.
3.
The continuity of the air barrier at building element assemblies that
enclose conditioned space or provide a boundary between conditioned space and
unconditioned space shall be identified.
4.
Documentation of the continuous air barrier shall detail methods of sealing
the air barrier such as wrapping, caulking, gasketing, taping or other approved
methods at the following locations:
i.Joints around fenestration and door frames.
ii.Joints between walls and floors, between walls at building corners,
between walls and roofs including parapets and copings, where
above-grade walls meet foundations and similar intersections.
iii.Penetrations or attachments through the continuous air barrier in
building envelope roofs, walls, and floors.
iv.Building assemblies used as ducts or plenums.
v.Changes in continuous air barrier materials and assemblies.
vi.Transition from one wall or roof assembly type to another such as,
but not limited to, transition between opaque wall system and glazed
wall system, and transition between a curtain wall glazed wall system
and a storefront glazed wall system.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
11 | P a g e
5.
Identify where testing will or will not be performed in accordance with
Section C402.5.2. Where testing will not be performed, a plan for field
inspections required by C402.5.2.3 shall be provided that includes the following:
i.Schedule for periodic inspection(s),
ii.Continuous air barrier scope of work,
iii.List of critical inspection items,
iv.Inspection documentation requirements, and
v.Provisions for corrective actions where needed.
C402.5.1.2 Renumber Section C402.5.1.1 as Section C402.5.1.2 and make the following
changes:
In Part 3, delete “Joints and seams associated with penetrations shall be sealed in the
same manner or taped”
In Part 3, replace “from wind stack effect and mechanical ventilation” with “pressure”.
In Part 4, replace “C402.5.10” with “C402.5.1.2.1”.
C402.5.1.2.1 Add Section C402.5.1.2.1 as follows:
C402.5.1.2.1 Electrical and communication boxes. Electrical and communication
boxes that penetrate the air barrier of the building thermal envelope, and that do not
comply with C402.5.1.2.1.1, shall be caulked, taped, gasketed, or otherwise sealed to the
air barrier element being penetrated. All openings on the concealed portion of the box
shall be sealed. Where present, insulation shall rest against all concealed portions of the
box.
C402.5.1.2.1.1 Add Section C402.5.1.2.1.1 as follows:
C402.5.1.2.1.1 Air-sealed boxes. Where air-sealed boxes are installed, they shall be
marked in accordance with NEMA OS 4. Air-sealed boxes shall be installed in
accordance with the manufacturer's instructions.
C402.5.1.3 Delete Section C402.5.1.3
C402.5.1.4 Delete Section C402.5.1.4
C402.5.1.5 Delete Section C402.5.1.5
C402.5.2 Replace Section C402.5.2 with the following:
C402.5.2 Air leakage compliance. Air leakage of the building thermal envelope shall be
tested by an approved third party in accordance with C402.5.2.1. The measured air leakage
shall not be greater than 0.35 cfm/ft2 (1.8 L/s × m2) of the building thermal envelope area at a
pressure differential of 0.3 inch water gauge (75 Pa) with the calculated building thermal
envelope surface area being the sum of the above- and below-grade building thermal
envelope.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
12 | P a g e
Exceptions:
1.
Where the measured air leakage rate is greater than 0.35 cfm/ft2 (1.8 L/s ×
m2) but is not greater than 0.45 cfm/ft2 (2.3 L/s × m2), the approved third party
shall perform a diagnostic evaluation in accordance with ASTM E1186. All
identified leaks shall be sealed where such sealing can be made without damaging
existing building components. A report specifying the corrective actions taken to
seal leaks shall be deemed to establish compliance with the requirements of this
section where submitted to the code official and the building owner. Where the
measured air leakage rate is greater than 0.45 cfm/ft2 (2.3 L/s × m2), corrective
actions must be made to the building and an additional test completed for which
the results are 0.45 cfm/ft2 (2.3 L/s × m2), or less.
2.
As an alternative, buildings or portions of buildings, containing Group R
and I occupancies, shall be permitted to be tested by an approved third party in
accordance with C402.5.2.2. The reported air leakage of the building thermal
envelope shall not be greater than 0.27 cfm/ft2 (1.4 L/s x m2) of the testing unit
enclosure area at a pressure differential of 0.2 inch water gauge (50 Pa).
C402.5.2.1 Add Section C402.5.2.1 as follows:
C402.5.2.1 Whole building test method and reporting. The building thermal envelope
shall be tested for air leakage in accordance with ASTM E3158 or an equivalent
approved method. A report that includes the tested surface area, floor area, air by volume,
stories above grade, and leakage rates shall be submitted to the code official and the
building owner.
Exceptions:
1.
For buildings less than 10,000 ft2 (1000 m2) the entire building thermal
envelope shall be permitted to be tested in accordance with ASTM E779, ASTM
E3158 or ASTM E1827 or an equivalent approved method.
2.
For buildings greater than 50,000 ft2 (4645 m2), portions of the building
shall be permitted to be tested and the measured air leakage shall be area-
weighted by the surface areas of the building thermal envelope in each portion.
The weighted average tested air leakage shall not be greater than the whole
building leakage limit. The following portions of the building shall be tested:
i.The entire building thermal envelope area of stories that have any
conditioned spaces directly under a roof.
ii.The entire building thermal envelope area of stories that have a
building entrance, a floor over unconditioned space, a loading dock,
or that are below grade.
iii.Representative above-grade portions of the building totaling not less
than 25 percent of the wall area enclosing the remaining conditioned
space.
C402.5.2.2 Renumber Section C402.5.2 as new Section C402.5.2.2 and make the following
changes:
Add “ASTM E3158,” after “ASTM E1827”
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
13 | P a g e
Replace “Units shall be tested separately with an unguarded blower door test as follows:”
with “Units shall be tested without simultaneously pressurizing adjacent units and shall
be separately tested as follows”.
In part 2 add “a middle floor unit” between “including a top floor unit” and “a ground
floor unit”
In part 2, replace “two units shall be tested” with “three units shall be tested”
Add new Part 3 as follows: “Enclosed spaces with not less than one exterior wall in the
building thermal envelope shall be tested in accordance with C402.5.3.”
Add the following exception “Exception: Corridors, stairwells, and enclosed spaces
having a conditioned floor area not greater than 1,500 ft2 shall be permitted to comply
with Section C402.5.1.5 and either Section C402.5.1.3 or C402.5.1.4.”
C402.5.2.3 Renumber Section C402.5.1.5 as Section C402.5.2.3 and make the following
changes:
Add “In addition to the requirements of Sections C402.5.2.1 and C402.5.2.2” after
“verification criteria” and before “the installation of the continuous air barrier”.
In part 2, replace “components and assemblies” with “materials, assemblies, and
systems”
In part 2, delete “while the air barrier is still accessible for inspection”
In part 2, replace “Sections C402.5.1.3 and C402.5.1.4” with “Sections C402.5.2.3.1 or
C402.5.2.3.2” and add “The air barrier shall remain accessible for inspection and repair”
C402.5.2.3.1 Renumber Section C402.5.1.3 as new Section C402.5.2.3.1.
C402.5.2.3.2 Renumber Section C402.5.1.4 as new Section C402.5.2.3.2.
C402.5.3 Renumber Section C402.5.4 as Section C402.5.3 and make the following changes:
Replace “shall meet the provisions of Table C402.5.4” with “shall comply with Table
C402.5.3”.
Add “conducted by an accredited, independent testing laboratory” between “Testing
shall be” and “in accordance with”
Replace “reference test standard in C402.5.4 by an accredited, independent testing
laboratory” with “reference test standard in Table C402.5.3”.
In Exception 1, replace “C402.5.1” with “C402.5.1.2”
In Exception 2, replace “comply with the testing alternative of Section C402.5,” with
“are tested for air leakage in accordance with Section C402.5.2”
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
14 | P a g e
In Exception 2, replace “Table C402.5.4” with “Table C402.5.3”
Relabel “Table C402.5.4” to “Table C402.5.3”
C402.5.4 Renumber Section C402.5.5 as Section C402.5.4 and make the following changes:
In Part 2.1, delete “Table C402.1.3 or”.
In Part 2.2 replace “Section C402.5.1.1” with “Section C402.5.1.2”.
In Part 2.4 replace “Water lines” with “Piping serving as part of a heating or cooling
system”.
C402.5.5 Renumber Section C402.5.6 as Section C402.5.5 and make the following changes:
Replace “Section C402.5.4” with “Section C402.5.3”.
C402.5.6 Renumber Section C402.5.7 as Section C402.5.6.
C402.5.7 Renumber Section C402.5.8 as C402.5.7 and make the following changes:
Replace “infiltration” with “air leakage”.
C402.5.8 Renumber Section C402.5.9 as Section C402.5.8 and make the following changes:
C402.5.9 Renumber Section C402.5.10 as Section C402.5.9.
In part 2 replace “more” with “greater”
In part 2 replace “when” with “where”
C402.5.10 Renumber Section C402.5.11 as Section C402.5.10 and make the following changes:
Replace “and lower the heating setpoint to 55°F (13°C)” with “and lower the heating
setpoint to 50°F (10°C)”
In Exception 1, add “operable openings into” before “separately-zoned areas”
In Exception 2, replace “warehouses” with “storage occupancies”
In Exception 3, revise to read: “Doors located in the exterior wall that are part of a
vestibule system”.
Add new Exception 4, “Operable openings used as part of a designed system for natural
ventilation.”
C402.5.10.1 Renumber Section C402.5.11.1 as Section C402.5.10.1
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
15 | P a g e
C402.6 Add Section C402.6 as follows:
C402.6 Approved calculation software tools. The following software tools are sufficient to
demonstrate compliance with Sections C401.2.1 Prescriptive Compliance and C402.7.
1. COMcheck-Web available at: https://www.energycodes.gov/comcheck
C402.7 Add Section C402.7 and subsections as follows:
C402.7 Derating and Thermal Bridges
C402.7.1 General. In addition to pre-calculated assembly U-factors, C-factors, or F-
factors outlined in Appendix A of ASHRAE 90.1 2019, vertical envelope performance
shall also take into account the effect of thermal bridges according to both C402.7.2 and
C402.7.3. In addition, the thermal resistance of spandrel sections within glazed wall
systems shall be according to C402.7.4. Together with Appendix A of ASHRAE 90.1
2019, these derated values and spandrel section values shall be used when showing
compliance with Section C402.1.4 or Section C402.1.5, as applicable.
C402.7.2 Continuous Insulation for Vertical Walls. Installed vertical wall continuous
insulation shall be derated using either C402.7.2.1, C402.7.2.2 or C402.7.2.3 to account
for the effect of fasteners through the continuous insulation.
C402.7.2.1. Prescriptive Derating. Derate vertical wall continuous insulation
using Equation C402.7.2.1 and a derating factor from C402.7.2.1.1 for portions of
wall having brick veneer systems, and a derating factor from C402.7.2.1.2 or
C402.7.2.1.3 for portions of wall having cladding systems.
Rderated = Ro x Derating Factor
(Equation C402.7.2.1)
where:
Rderated =
R value after derating, to be used when showing
compliance R402.7.2
Ro =
R value of the continuous insulation prior to derating
Derating Factor =
Derating factor from C402.7.2.1.1, C402.7.2.1.2, or
C402.7.2.1.3
C402.7.2.1.1 Brick Veneer Systems. Wall systems comprised of brick
veneer anchored to the building with fasteners shall use a Derating Factor
of 0.7 to account for the clear field thermal bridge derating effect of the
fasteners. In addition, brick shelf angles shall be derated according to
Section C402.7.3 to account for the linear thermal bridge derating effect
of any brick shelf angles.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
16 | P a g e
C402.7.2.1.2 Cladding Systems. Wall systems comprised of cladding
systems shall use a derating factor per Table 402.7.2.1.2
Table 402.7.2.1.2 Cladding System Derating Factors
Thickness of Ro
Derating Factor
Ro is less than or equal to R-15
Derating Factor = 0.74 – 0.021 x Ro
Ro is greater than R-15
Derating Factor = 0.55 – 0.007 x Ro
C402.7.2.1.3 Cladding Systems with Qualifying Thermal Breaks. If
plastic or fiberglass fasteners entirely comprised of material having
thermal conductivity of 3 Btu-in/hr-ft2-F or less are used to support
external cladding; or, if fasteners having thermal breaks which have a
conductivity of 3 Btu-in/hr-ft2-F or less on both ends of the fastener are
used to support external cladding, use Derating Factor of 0.8.
C402.7.2.2. Reference Derating. Use pre-solved, derated continuous insulation
values contained in Building Envelope Thermal Bridging Guide, version 1.6 or
higher, published by BC Hydro Power Smart at https://www.bchydro.com
C402.7.2.3. Modelled Derating. Use two or three-dimensional finite element
analysis heat transfer model to calculate derated value. A three-dimensional
model shall be used when there are point thermal bridges or thermal bridging in
multiple planes.
C402.7.3. Linear Thermal Bridges. In addition to derating per Section C402.7.2,
installed vertical wall insulation U values shall be further derated for linear thermal
bridges where the vertical wall intersects the following: brick shelf angles, balconies,
vertical interior walls, horizontal interior walls, windows, roof, other vertical walls on
different plane, and grade using Equation C402.7.3.
𝑈𝑑𝑒𝑟𝑎𝑡𝑒𝑑=
𝑃𝑆𝐼 ∗ 𝐿𝑒𝑛𝑔𝑡ℎ
𝐴𝑡𝑜𝑡𝑎𝑙
+ 𝑈𝑜
(Equation C402.7.3)
where:
Uderated =
Derated wall U value (Btu/hr-ft2-F)
PSI
=
Value from Section C402.7.3.1, C402.7.3.2, or C402.7.3.3 (Btu/hr-ft-F)
Length =
Length of linear thermal bridge (ft)
Atotal =
Area of derated wall (ft2)
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
17 | P a g e
Uo
=
Wall or roof U value prior to linear thermal bridge derating
C402.7.3.1 Prescriptive PSI values. Use PSI values from Table
C402.7.3.1
Table C402.7.3.1 Linear Thermal Bridge Prescriptive PSI values.
Type of Linear Thermal Bridge
PSI-value
(Btu/hr - ft – F)
Balcony to exterior vertical wall intersection
1.00
Intermediate floor to exterior vertical wall intersection
0.60
Interior vertical wall to exterior vertical wall intersection
0.50
Fenestration to exterior vertical wall intersection
0.32
Parapet (vertical wall to roof intersection)
0.60
Brick shelf angle
0.35
Vertical wall to grade intersection
0.52
Vertical wall plane transition (building corners and other
changes in vertical wall plane)
0.25
C402.7.3.2. Reference PSI Values. Use pre-solved PSI values contained in
Building Envelope Thermal Bridging Guide, version 1.6 or higher, published by
BC Hydro Power Smart.
C402.7.3.3. Modelled PSI Values. Use a two or three-dimensional finite
element analysis to calculate PSI values. A three-dimensional model shall be used
when there are point thermal bridges or thermal bridging in multiple planes.
C402.7.4 Thermal Resistance of Spandrel Sections. R-factor of opaque spandrel
sections within curtain wall systems shall be accordance with C402.7.4.1, C402.7.4.2, or
C402.7.4.3.
C402.7.4.1 Prescriptive R value. Opaque spandrel sections within glazed wall
systems shall have at least R-12 insulation. For the purpose of calculating
weighted U value in accordance with Section C402.1.5, spandrel sections shall
use values in Table C402.7.4.1.
Table C402.7.4.1 Spandrel Section Default R values
Type
Default R-Value
Thermally broken
3.5
Non-thermally broken
2
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
18 | P a g e
C402.7.4.2. Reference R values. Use pre-solved opaque spandrel sections R
values contained in Building Envelope Thermal Bridging Guide, version 1.6 or
higher, published by BC Hydro Power Smart.
C402.7.4.3. Modelled R values. Use a two or three-dimensional finite element
analysis to calculate R value of opaque spandrel section. A three-dimensional
model shall be used when there are point thermal bridges or thermal bridging in
multiple planes.
C403.5 Modify Section C403.5 as follows
Add “Dedicated outside air systems” as Item 4 of the list of where air or water economizers
shall be provided.
Delete exception 5 and renumber subsequent exceptions to reflect deletion.
Table C403.5(1). Show only Climate Zone 5A.
Table C403.5(2). Delete this table
C403.7.4 Replace Subsection C403.7.4 with the following:
C403.7.4 Energy Recovery Systems. Energy recovery ventilation systems shall
be provided as specified in Section C403.7.4.1, as applicable and C403.7.4.2.
C403.7.4.1 Modify Section C403.7.4.1 as follows:
Replace “not less than 60 percent at heating design condition.” with “not less than 75 percent at
heating design condition. Outdoor air must be delivered directly to the dwelling unit. The
building weighted average sensible energy recovery effectiveness must meet the requirements of
C403.7.4.2.”
Delete all the exceptions (exceptions 1 through 4).
C403.7.4.2 Modify Section C403.7.4.2 as follows:
Replace “The energy recovery system shall provide an enthalpy recovery ratio of not less
than 50% at design conditions” with “The energy recovery system shall result in either 1
or 2, as applicable”
Add 1 and 2 as follows
1. A sensible recovery ratio of at least 50% at heating design conditions for
systems that provide makeup for Class 3 or 4 exhaust. The requirement
can be satisfied either for each fan system individually or based on a
weighted average of the ventilation air flow for all applicable fan systems
in the entire building per Equation C403.7.4.2(1).
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
19 | P a g e
Equation C403.7.4.2(1)
Weighted average sensible energy recovery ratio = [sensible energy
recovery ratio for fan system 1 x outside air flow for system 1 + sensible
energy recovery ratio for fan system 2 x outside air flow for system 2 + …
]/[outside air flow for system 1 + outside air flow for system 2 + …]
2. An enthalpy recovery ratio of not less than 70% at heating and cooling
design conditions for all other systems. The requirement can be satisfied
either for each fan system individually or based on a weighted average of
the ventilation air flow for all applicable fan systems in the entire building
per Equation C403.7.4.2(2).
Equation C403.7.4.2(2)
Weighted average enthalpy energy recovery ratio = [enthalpy recovery
ratio for fan system 1 x outside air flow for system 1 + enthalpy recovery
ratio for fan system 2 x outside air flow for system 2 + … ]/[outside air
flow for system 1 + outside air flow for system 2 + …]
Delete exceptions 2 (including 2.1 and 2.2), 4, 5, 6, 7, and 8
Renumber exception 3 as exception 2
Renumber exception 9 as exception 3 and change from “20 hours per week” to “10 hours
per week
Renumber exception 10 as exception 4
Renumber exception 11 as exception 5
Revise Tables C403.7.4.2(1) and C403.7.4.2(2) and show only Climate Zone 5A row, as follows:
Table C403.7.4.2(1) ENERGY RECOVERY REQUIREMENT (Ventilation systems
operating less than 8,000 hours per year)
Climate
Zone
PERCENT (%) OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE
>=10%
and <20%
>=20%
and < 30%
>=30%
and < 40%
>=40%
and <50%
>=50%
and <60%
>=60%
and <70%
>=70%
and <80%
>=80%
Design Supply Fan Airflow Rate (cfm)
5A
10,000
8,000
2,750
0
0
0
0
0
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
20 | P a g e
Table C403.7.4.2(2) ENERGY RECOVERY REQUIREMENT (Ventilation systems operating note
less than 8,000 hours per year)
Climate
Zone
PERCENT (%) OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE
>=10%
and <20%
>=20%
and < 30%
>=30%
and < 40%
>=40%
and <50%
>=50%
and <60%
>=60%
and <70%
>=70%
and <80%
>=80%
Design Supply Fan Airflow Rate (cfm)
5A
0
0
0
0
0
0
0
0
C405.2.4 Modify Section C405.2.4 as follows
In item 1, replace “150 watts” with “100 watts”
In item 3, replace “150 watts” with “100 watts”
C405.13 Add Section C405.13 as follows:
C405.13 Electric Vehicle Ready Parking Spaces (“EV Ready Spaces”) (Mandatory). New
parking spaces shall provide EV Ready Spaces in accordance with Table C405.13. Installed
wiring suitable for 6.6kW or higher SAE J1772-2017 AC Level II EVSE shall be connected to
the service panel and run to within 6 feet (1828mm) of any qualifying parking space. Conductors
and outlets for EVSE shall be sized and installed in accordance with the MA electrical code.
TABLE C405.13 EV-READY SPACE REQUIREMENTS
Occupancy
Classification
Minimum percentage
of EV-Ready Spaces
EV Charging Performance Requirements
Group R and Group
B
20%
40-amp dedicated branch circuit or larger branch
circuit with ALMS in accordance with Table
C405.13.1
All Other
Occupancies
10%
40-amp dedicated branch circuit or larger branch
circuit with ALMS in accordance with Table
C405.13.1
Exceptions:
1. Parking spaces and garage spaces intended exclusively for storage of vehicles
for retail sale or vehicle service are excluded from the EV-ready space
percentage calculation.
2. Any parking facility with 4 or more spaces providing installed Direct Current
fast charging EVSE with a minimum charging speed of 150 kW to each space.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
21 | P a g e
3. One or more AC Level II spaces may be substituted with multiple AC Level I
spaces provided with wiring for a minimum 20amp, 120-volt EVSE, with a
ratio of at least 3 AC Level I spaces for each AC Level II space required.
4. Parking spaces specifically designated for medium or heavy-duty vehicles are
excluded from the EV-ready space percentage calculation.
C405.13.1 Add Section C405.13.1 as follows:
C405.13.1 Minimum Charging Performance Requirements. Automatic Load Management
System (ALMS) may be used to control electric vehicle loads for EV-Ready or EVSE-Installed
Spaces with AC Level II or Level I charging, subject to the performance requirements in Table
C405.13.1. The maximum number of parking spaces that may share a single branch circuit varies
based on the percentage of all parking spaces to be provided with EVSE.
TABLE C405.13.1 EV-READY PERFORMANCE REQUIREMENTS
Circuit Breaker Amperage
Maximum Parking Spaces
that May Share a Branch
Circuit with 10%-60% EV
Ready spaces
Maximum Parking Spaces
that May Share a Branch
Circuit with 61-100% EV
Ready spaces
40A
1
2
50A
1
2
60A
2
4
70A
3
6
80A
4
8
90A
5
9
100A
6
10
C405.13.2 Add Section C405.13.2 as follows:
C405.13.2 Identification. Construction documents shall indicate the branch circuit termination
point and proposed location of future EVSE. Construction documents shall also provide
information on amperage of future EVSE, wiring schematics, Automatic Load Management
Systems, and electrical load calculations to verify that the electrical panel service capacity and
electrical system, including any on-site distribution transformers, have sufficient capacity to
simultaneously charge all EVs at all required EV ready spaces.
C406.1 Modify Section C406.1 as follows:
Replace “shall achieve a total of 10 credits” with “shall achieve a total of 15 credits”
Table C406.1(1) Modify Table C406.1(1) as follows:
Delete rows for C406.2.1: 5% heating efficiency improvement and C406.7.3: Efficient
fossil fuel water heater
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
22 | P a g e
Replace row for option C406.2.3: 10% heating efficiency improvement with the
following:
Section
Climate Zone 5A
C406.2.3 Renewable space heating
15
Add the following row for option C406.13:
Section
Climate Zone 5A
C406.13 Heavy Timber Construction
8
Table C406.1(2) Modify Table C406.1(2) as follows:
Delete rows for C406.2.1: 5% heating efficiency improvement and C406.7.3: Efficient
fossil fuel water heater
Replace row for option C406.2.3: 10% heating efficiency improvement with the
following:
Section
Climate Zone 5A
C406.2.3 Renewable space heating
15
Add the following row for option C406.13:
Section
Climate Zone 5A
C406.13 Heavy Timber Construction
8
Table C406.1(3) Modify Table C406.1(3) as follows:
Delete rows for C406.2.1: 5% heating efficiency improvement and C406.7.3: Efficient
fossil fuel water heater
Replace row for option C406.2.3: 10% heating efficiency improvement with the
following:
Section
Climate Zone 5A
C406.2.3 Renewable space heating
15
Add the following row for option C406.13:
Section
Climate Zone 5A
C406.13 Heavy Timber Construction
8
Table C406.1(4) Modify Table C406.1(4) as follows:
Delete rows for C406.2.1: 5% heating efficiency improvement and C406.7.3: Efficient
fossil fuel water heater
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
23 | P a g e
Replace row for option C406.2.3: 10% heating efficiency improvement with the
following:
Section
Climate Zone 5A
C406.2.3 Renewable space heating
15
Add the following row for option C406.13:
Section
Climate Zone 5A
C406.13 Heavy Timber Construction
8
Table C406.1(5) Modify Table C406.1(5) as follows:
Delete rows for C406.2.1: 5% heating efficiency improvement and C406.7.3: Efficient
fossil fuel water heater
Replace row for option C406.2.3: 10% heating efficiency improvement with the
following:
Section
Climate Zone 5A
C406.2.3 Renewable space heating
15
Add the following row for option C406.13:
Section
Climate Zone 5A
C406.13 Heavy Timber Construction
8
C406.1.1 Modify Section C406.1.1 as follows:
Replace “minimum number of 5 credits” with “minimum number of 10 credits”
C406.2.1 Delete this section
C406.2.3 Replace Section C406.2.3 with the following:
C406.2.3. Renewable space heating. All space heating shall be provided with cold-climate air
source heat pumps having rated coefficient of performance (COP) of at least 1.75 at 5 degrees
Fahrenheit source air, or ground source heat pumps.
C406.7.3 Delete this section
C406.9 Replace Section C406.9 with the following:
C406.9 Reduced air leakage. Air leakage of the building thermal envelope shall be tested by an
approved third party in accordance with Section C402.5.2.1. The measured air leakage shall not
exceed 0.20 cfm/ft2 (1.1 L/s × m2) of the building thermal envelope at a pressure differential of
0.3 inches water gauge (75 Pa), with the calculated surface area being the sum of the above- and
below-grade building thermal envelope.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
24 | P a g e
C406.13 Add Section C406.13 as follows:
C406.13 Heavy Timber construction. For buildings with 4 stories or more of Type IV heavy
timber construction either above grade, or above a podium.
C407 Replace Section C407 in its entirety with the following:
C407.1 Targeted Performance
This option requires compliance with Sections C407.1.1 through C407.1.2.
C407.1.1 Compliance. Buildings shall comply with Sections C407.1.1.1 through
C407.1.1.6.
C407.1.1.1 Building performance modeling
Building performance modeling shall be used to show compliance with
C407.1.1.5. The simulation program shall be a computer-based program for the
analysis of energy consumption in buildings. The simulation shall include
calculation methodologies for the building components being modeled and meet
the requirements in ANSI/ASHRAE/IESNA 90.1-2019 Appendix G Section
G2.2.1(a)-(d) and Section G2.2.4.
C407.1.1.2 Climatic Conditions
The simulation program shall perform the simulation using hourly values of
climatic data using representative weather files prescribed by the Massachusetts
Department of Energy Resources.
C407.1.1.3 Modeling Building Envelope Infiltration. The air leakage rate of the
building envelope shall be modeled following ANSI/ASHRAE/IESNA 90.1-2019
Section G3.1.1.4.
C407.1.1.4 Internal loads, scheduling, and other modeling assumptions
Performance modeling shall use the internal load, scheduling, and other
assumptions as prescribed by the Massachusetts Department of Energy Resources.
C407.1.1.5 Thermal energy demand intensity (TEDI) limits
Performance modeling shall show that the building’s heating thermal energy
demand intensity and cooling thermal energy demand intensity are less than or
equal to the values in Table C407.1.1.5
Table C407.1.1.5 Thermal Energy Demand Intensity (TEDI) Limits
Use Type
Heating TEDI
(kBtu/sf-yr)
Cooling TEDI
(kBtu/sf-yr)
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
25 | P a g e
Office, fire station, library, police station, post
office, town hall >= 125,000-sf
1.5
23
Office, fire station, library, police station, post
office, town hall between 75,000 and 125,000-sf
4 – 0.00002 *
Area (sf)
18 + 0.00004 *
Area (sf)
Office, fire station, library, police station, post
office, town hall <= 75,000-sf
2.5
21
K-12 School >= 125,000-sf
2.2
12
K-12 School between 75,000 and 125,000-sf
2.7 – 0.000004
* Area (sf)
32 - 0.00016 *
Area (sf)
K-12 School <= 75,000-sf
2.4
20
Residential multifamily and dormitory >= 125,000-
sf
2.8
22
Residential multifamily and dormitory between
75,000 and 125,000-sf
3.8 – 0.000008
* Area (sf)
4.5 + 0.00014 *
Area (sf)
Residential multifamily and dormitory <= 75,000-sf
3.2
15
All other >= 125,000-sf
1.5
23
All other between 75,000 and 125,0000-sf
4 – 0.00002 *
Area (sf)
18 + 0.00004 *
Area (sf)
All other <= 75,000-sf
2.5
21
C407.1.1.6 Mixed use buildings
For buildings having more than one use type where any use type is more than
10% of the total space conditioned aera, each separate use type having more than
10% of the total space conditioned area shall separately and individually show
compliance with C407.1.1.5 for that respective use type. Use types having less
than or equal to 10% of the total space conditioned area do not have to show
separate, individual compliance with C407.1.1.5 but can be incorporated into and
treated as the majority use type.
C407.1.2 Documentation. Simulated performance shall be documented, and
documentation shall be submitted to the rating authority. Documentation shall include all
the assumptions used in the performance modeling such that the documentation can be
used as a specification checklist for implementation during design and construction. The
information shall be submitted in a report and shall include the items described in
ANSI/ASHRAE/IESNA 90.1-2019 Appendix G Section G1.3.2 Parts b, g, h, i, j, k, l, n,
o, and q, and Section G1.3.3.
C407.2 Relative Performance. This option requires compliance with Section C407.2.1 and
C407.2.2
C407.2.1 Electrification and Documentation of Highly Ventilated Buildings.
Buildings using the Relative Performance Pathway (C407.2) because average ventilation
at full occupancy is greater than 0.5 cfm/sf shall have space heating electrified in
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
26 | P a g e
accordance with Section C401.4.1 and shall submit design documents showing
ventilation system design and air flow rates as required by Section C103.2 part 16.
C407.2.2 Compliance. Building shall comply with ANSI/ASHRAE/IESNA 90.1-2019
Section 4.2 using the Appendix G pathway as modified by C407.2.2.1 and C407.2.2.2.
C407.2.2.1 Modification to ANSI/ASHRAE/IESNA 90.1-2019 Section 4.2.
ANSI/ASHRAE/IESNA 90.1-2019 Section 4.2 Replace 4.2.1.1 with the following:
New buildings shall comply with 4.2.2 through 4.2.5 and normative Appendix G.
When using Normative Appendix G, the Performance Energy Index (PEI) of new
buildings, additions to existing buildings, and alterations to existing buildings
shall be less than or equal to the Performance Energy Index Target (PEIt) when
calculated in accordance with the following:
PEIt = [BBUE + (BPF x BBRE)]/BBSE
where:
PEI
=
Performance Energy Index calculated in accordance with Section
G1.2
BBUE =
Baseline building unregulated site energy
BBRE =
Baseline building regulated site energy
BPF
=
Building performance factor from Table 4.2.1.1 For building area
types not listed in Table 4.2.1.1 use “All others”. Where a building has
multiple area types, the required BPF shall be equal to the area-weighted
average of the building area types.
BBSE =
Baseline building site energy (sum of BBUE and BBRE)
ANSI/ASHRAE/IESNA 90.1-2019 Section 4.2 Revise Table 4.2.1.1 to show only Climate Zone
5A; remove multifamily, office, and school; and adjust the BPFs as follows:
Table 4.2.1.1 Building Performance Factor (BPF)
Building Area Type
Climate Zone 5A
Health care/hospital
0.59
Hotel/motel
0.57
Restaurant
0.62
Retail
0.47
Warehouse
0.41
All others
0.51
C407.2.2.2 Modification to ANSI/ASHRAE/IESNA 90.1-2019 Appendix G
ANSI/ASHRAE/IESNA 90.1-2019 Appendix G In all Sections of Appendix G, replace
references to “baseline building performance” with “baseline building site energy”, replace
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
27 | P a g e
“proposed building performance” with “proposed building site energy”, replace “energy cost
savings” with “site energy savings”
ANSI/ASHRAE/IESNA 90.1-2019 Appendix G Replace G1.2.2 with following, keeping the
exception unchanged:
The site energy of the proposed design is calculated in accordance with the
provisions of this appendix using the following formula:
Performance energy index (PEI) = Proposed building site energy / baseline
building site energy (BBSE)
Both the proposed building site energy and the baseline building site energy shall
include all end use load components within and associated with the building when
calculating the performance energy index.
ANSI/ASHRAE/IESNA 90.1-2019 Appendix G Delete G1.3.2 Part m and Part p
ANSI/ASHRAE/IESNA 90.1-2019 Appendix G Delete G2.1 Part c
ANSI/ASHRAE/IESNA 90.1-2019 Appendix G Revise G2.4.1 as follows
Site recovered energy shall be subtracted from the proposed building site energy
when calculating performance. Energy used to recharge vehicles that are used for
on-road and off-site transportation purposes, or energy losses from use of behind-
the-meter energy storage, should not be included when calculating performance.
On-site renewable energy shall not be subtracted from the proposed building site
energy when calculating performance.
ANSI/ASHRAE/IESNA 90.1-2019 Appendix G Delete G2.4.2
ANSI/ASHRAE/IESNA 90.1-2019 Appendix G Add the following row to Section G Table G3.1.1-
1.
TABLE G3.1.1-1 BASELINE BUILDING VERTICAL FENESTRATION
PERCENTAGE OF GROSS ABOVE-GRADE-WALL AREA
Building Area Types
Baseline Building Gross Above-Grade-Wall Area
Multifamily
24%
Section C407.3 Add Section C407.3 as follows:
C407.3 Passive House. This option requires compliance with Section C407.3.1 and C407.3.2.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
28 | P a g e
C407.3.1 Compliance. Buildings shall be pre-certified as meeting the Phius CORE 2021
or Phius ZERO 2021 Passive Building Standard – North America, or newer, demonstrated
using Phius approved software, where Phius Design-Certification is demonstrated by Phius
and a Certified Passive House Consultant (CPHC); or, Projects pre-certified as meeting the
Certified Passive House standard using the current software and program criteria by the
Passive House Institute (PHI), where PHI certification is demonstrated by a Certified
Passive House Designer and a Certified Passive House Certifier.
C407.3.2 Documentation. Compliance with Phius or PHI shall be in accordance with
C407.3.3.1 or C407.3.3.2
C407.3.2.1 Phius Documentation. When using WUFI Passive or other Phius-
approved software:
1. Prior to the issuance of a building permit, the following item(s) must be provided
to the Building Official:
a. A Phius 2021 (or newer) Verification Report which demonstrates project
compliance with Phius 2021 (or newer) performance requirements.
b. A statement from the CPHC that the verification report results accurately
reflect the plans submitted.
c. Evidence of project registration from Phius.
OR
a. A Design Certification Letter from Phius.
2. Prior to the issuance of a certificate of occupancy, the following items must be
provided to the building official:
a. Design Certification Letter from Phius.
b. An updated Verification Report by the CPHC which reflects “as-built”
conditions and test results that demonstrate project compliance with
Phius (blower door and ventilation results).
c. A statement from the CPHC that the envelope meets the Phius
hygrothermal requirements found in Appendix B of the Phius 2021
Certification guidebook
d. A statement from the Phius Certified Verifier or Rater that the project
test results and other Phius verification requirements are met.
e. A copy of the Phius workbook listing all testing results and as-built
conditions.
OR
a. A Project Certificate demonstrating final certification awarded by Phius.
AND
f. A statement from the Phius Verifier or Rater of compliance with
C405.13: EV ready, and Appendix CB: Solar Ready Provisions.
C407.3.2.2 Passive House International (PHI) Documentation.
1. If using PHI Passive House software, prior to the issuance of a building permit, the
following item(s) must be provided to the Building Official:
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
29 | P a g e
a. A PHPP compliance report which demonstrates project compliance with
current PHI performance requirements;
b. A statement from the Certified Passive House Consultant/Designer (CPHC/D)
that the PHPP results and compliance report accurately reflect the plans
submitted;
c. Evidence of project registration from a Certified Passive House Certifier.
OR
a. A Design Certification Letter from a Certified Passive House Certifier.
2. Prior to the issuance of a certificate of occupancy, the following items must be
provided to the building official:
a. A Design Certification Letter from a Certified Passive House Certifier.
b. An updated PHPP compliance report which reflects “as-built” conditions and
test results (blower door and ventilation results) that demonstrates project
compliance with PHI performance requirements;
c. A copy of the Passive House Verifier’s or Rater’s test results;
d. A statement from the CPHD that the project test results meet the model
performance requirements, all the mandatory limits and any other mandatory
requirements.
OR
a. A Final Certification Letter from a Certified Passive House Certifier
AND
e. A statement from the Passive House Verifier or Rater of compliance with
C405.13: EV ready, and Appendix CB: Solar Ready Provisions.
Section C407.4 Add Section C407.4 as follows:
C407.4 HERS Index (HERS) for multi-family buildings. This option requires compliance
with Section C407.4.1, C407.4.2, C407.4.3
C407.4.1 Compliance. Each dwelling unit shall have a certified HERS Index (HERS)
rating less than or equal to the appropriate value indicated in Table C407.4 when compared
to the HERS index reference design for each dwelling unit prior to credit for onsite
renewable electric generation. Buildings shall meet or exceed ENERGY STAR
Multifamily New Construction (MFNC) program requirements. The Home Energy Rating
Index (HERS) shall be determined in accordance with RESNET/ICC Standard 301-2019.
Software tools used for determining HERS Index shall be Approved Software Rating Tools
in accordance with RESNET/ICC 301. Where calculations require input values not
specified by Sections R402, R403, R404 and R405, those input values shall be taken from
RESNET/ ICC 301.
TABLE C407.4 MAXIMUM ENERGY RATING INDEX
Maximum HERS Index scorea,
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
30 | P a g e
Building Energy
Sources
New
construction
permits until
June 30, 2024
New construction
permits after July 1,
2024
Major alterations,
additions, or Change
of useb
Mixed-fuel building
52
42
52
Solar Electric
Generation
55
42
55
All-Electric building
55
45
55
Solar Electric & All-
Electric building
58
45
58
a Maximum HERS rating prior to onsite renewable electric generation in accordance with
Section C407.4
b Alterations, Additions or Change of use covered by Section R503.1.5 are subject to this
maximum HERS rating.
C407.4.2 Documentation. Documentation verifying that the methods and accuracy of
compliance software tools conform to the provisions of this section shall be provided to
the building official in accordance with C407.4.3.1 and C407.4.3.2:
C407.4.2.1 Prior to issuance of building permit. Prior to the issuance if a building
permit, the following items must be provided to the Building Official:
1. Building street address, or other building site identification.
2. Declare the HERS Index on title page and building plans.
3. The name of the individual performing the analysis and generating the
compliance report.
4. The name and version of the compliance software tool.
5. Documentation of all inputs entered into the software used to produce the results
for the reference design and/or the rated home.
6. A certificate indicating that the proposed design has a HERS Index less than or
equal to the appropriate score indicated in Table C407.4 when compared to the
ERI reference design. The certificate shall document the building component
energy specifications that are included in the calculation, including: component
level insulation R-values or U-factors; assumed duct system and building
envelope air leakage testing results; and the type and rated efficiencies of
proposed heating, cooling, mechanical ventilation, and service water-heating
equipment to be installed. If on-site renewable energy systems will be installed,
the certificate shall report the type and production size of the proposed system.
7. When a site-specific report is not generated, the proposed design shall be based on
the worst-case orientation and configuration of the rated home.
C407.4.2.2 Prior to issuance of certificate of occupancy. Prior to the issuance of a
certificate of occupancy, the following items must be provided to the Building
Official:
1. Building street address or other building site identification.
2. Declaration of the Final HERS Index on title page and on building plans.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
31 | P a g e
3. The name of the individual performing the analysis and generating the report.
4. The name and version of the compliance software tool.
5. Documentation of all inputs entered into the software used to produce the results
for the reference design and/or the rated home.
6. A final confirmed certificate indicating that the confirmed rated design of the built
home complies with Sections C407.4. The certificate shall report the energy
features that were confirmed to be in the home, including: component-level
insulation R-values or U-factors; results from any required duct system and
building envelope air leakage testing; and the type and rated efficiencies of the
heating, cooling, mechanical ventilation, and service water-heating equipment
installed.
7. Documentation that each unit meets or exceeds ENERGY STAR Multifamily
New Construction (MFNC) program requirements.
8. Where on-site renewable energy systems have been installed on or in the home,
the certificate shall report the type and production size of the installed system.
9. Compliance with C405.13, and either Appendix CB or Appendix CC as
applicable
C407.4.3 Verification by approved agency. Verification of compliance shall be
completed by a certified HERS rater.
CHAPTER 5 [CE] EXISTING BUILDINGS
C501.2 Delete the exception
C502.1 Revise Section C502.1 as follows:
Add the following first sentence “Additions to an existing building where the addition is
up to 100% of the size of the existing building and less than 20,000-sf shall comply with
Sections C401.3, C402 through C406, and Section C408. Additions which exceed either
of these limits shall comply with the applicable pathway for new construction in C401.2.”
C502.2 Revise Section C502.2 as follows:
Remove both exceptions
C503.1 Revise Section C503.1 as follows:
Replace “the requirements of Section C503” with “the requirements of Sections C503,
C402, C403, C404, and C405”
Replace Exception 3 with “Where the component performance alternative in Section
402.1.5 is used to comply with this section, the proposed UA shall not be greater than
110 percent of the target UA.”
C505.1 Revise Section C505.1 as follows:
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
32 | P a g e
Replace “this code” with “Sections C401.3, C402 through C406, and Section C408”
Appendix CB Adopt unamended
APPENDIX CB: SOLAR-READY ZONE – COMMERCIAL.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
33 | P a g e
APPENDIX CC - MASSACHUSETTS MUNICIPAL OPT-IN
SPECIALIZED ENERGY CODE 2023
COMMERCIAL BUILDING PROVISIONS
The provisions contained in this appendix are not mandatory unless specifically referenced in the
adopting ordinance. The provisions contained in this appendix together with referenced sections from
the Stretch energy code constitute the Specialized opt-in code for commercial buildings, and may be
adopted by a city or town together with the Residential Specialized code Appendix RC as their stretch
energy code. When adopted by the local municipality, the provisions in this appendix are mandatory in
combination with the IECC2021 with Massachusetts Stretch code amendments.
SECTION CC101 GENERAL
CC101.1 Replace Section CC101 as follows:
CC101.1 Purpose. The purpose of this appendix is to form the commercial building provisions
of the Massachusetts Municipal Opt-in Specialized Code to supplement the Massachusetts
Stretch Energy Code and to provide a compliance pathway for buildings that require renewable
energy systems of adequate capacity to achieve net zero carbon.
CC101.2 Replace Section CC101.2 as follows:
CC101.2 Scope. This appendix applies to new buildings that are addressed by the Municipal
Opt-in Specialized Code. The Specialized Code maintains the energy efficiency requirements of
the Stretch Code for all building types except multi-family. CC103 lays out the additional clean
energy requirements for all building types.
Residential buildings and dwelling units within mixed use buildings shall comply as follows:
1) New dwelling units over 4,000 square feet in conditioned floor area in Mixed Fuel
Buildings shall comply with the Zero Energy pathway and Section CC103 or with
residential code Section RC102.
2) New R-use buildings over 12,000 square feet in conditioned floor area shall
comply in accordance with Table CC101.2.
3) New R-use buildings less than or equal to 12,000 square feet in conditioned floor
area shall comply with Residential Appendix RC.
TABLE CC101.2 MULTI-FAMILY AND R-USE COMPLIANCE
R-Use buildings
over 12,000 sf, or R-
Use portions over
12,000 sf in mixed-
use buildings
Compliance Path options by permit submittal date
C407.3
Passive House
C407.1
Targeted
Performance
C407.4
HERS Index
Up to 5 stories
Required from
Jan 1, 2023
6 stories and higher
Required from
Jan 1, 2024
Optional until
Jan 1, 2024
Optional until
Jan 1, 2024
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
34 | P a g e
Exceptions:
1. Detached one- and two-family dwellings and townhouses as well as Group R-2
buildings three stories or less in height above grade plane, manufactured homes
(mobile dwellings), and manufactured houses (modular dwellings). These buildings
and dwelling units shall comply with Residential Appendix RC under the Specialized
energy code.
2. Buildings that use neither electricity nor fossil fuel.
CC101.3 Add Section CC101.3 as follows:
CC101.3 Compliance. New buildings shall demonstrate compliance with Sections CC101.4,
CC101.5 and one of the following pathways:
1. Zero Energy pathway: Buildings shall comply with Section CC103 and demonstrate
that they are Zero Energy Buildings in accordance with Equation CC-1. Mixed Fuel
Buildings with any capacity for on-site fossil fuel use shall be pre-wired for future
electrification of all fuel uses in accordance with Section CC105.
2. All-Electric pathway: Buildings shall comply with Section CC104.
3. Mixed Fuel pathway: Mixed Fuel Buildings other than Zero Energy Buildings with any
capacity for on-site fossil fuel use shall comply with CC105 and CC106. The following
uses shall be excluded when determining whether new buildings will have on-site fossil
fuel use:
1) On-site back-up generators using fossil fuels
2) On-site refuelling of vehicles or outdoor equipment using fossil fuels
CC101.4 Add Section CC101.4 as follows:
CC101.4 Minimum building energy efficiency. New buildings shall comply with Section
C401.2.1 or C401.2.2. as prescribed in Section C401. Existing buildings shall comply with
Chapter 5 as amended.
CC101.5 Add Section CC101.5 as follows:
CC101.5 Minimum electric vehicle ready parking requirements. New parking spaces shall
provide electric vehicle ready spaces in accordance with Section C405.13 and Table C405.13.
SECTION CC102 DEFINITIONS
CC102 Add the following definitions:
NET ZERO EMISSIONS BUILDING. A building which is consistent with achievement of
MA 2050 net zero emissions, through a combination of highly energy efficient design together
with being either a Zero Energy Building, or an All-Electric Building, or where fossil fuels are
utilized, the building is fully pre-wired for future electrification and generates solar power on-site
from the available Potential Solar Zone Area.
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
35 | P a g e
POTENTIAL SOLAR ZONE AREA. The combined area of any flat roofs, or low-sloped roofs
and any steep-sloped roofs oriented between 90 degrees and 300 degrees of true north where the
annual solar access is 70 percent or greater. Annual solar access is the ratio of “annual solar
insolation with shade” to the “annual solar insolation without shade”. Shading from obstructions
located on the roof or any other part of the building shall not be included in the determination of
annual solar access.
ZERO ENERGY BUILDING. A building which through a combination of highly energy
efficient design and onsite renewable energy generation is designed to result in net zero energy
consumption over the course of a year as measured in MMBtus or KWheq, on a site energy basis,
excluding energy use for charging vehicles.
CC102 Delete the definitions for:Adjusted off-site renewable energy, zero energy performance
index (ZEPI PB/EE)
SECTION CC103 ZERO ENERGY PATHWAY MINIMUM RENEWABLE ENERGY
CC103.1 Modify Section CC103.1 as follows (keeping Table CC103.1 unchanged):
Delete “or off-site renewable energy shall be procured”
Equation CC-1 Replace Equation CC-1 with the following:
REonsite Ebuilding
(Equation CC-1)
where:
REonsite = Annual site energy production from on-site renewable energy systems (see
Section CC103.2).
Ebuilding = Building energy use without consideration of renewable energy systems, on-
site energy storage, on-site back-up generators, or on-site refuelling of vehicles or
outdoor equipment.
When Section C401.2.1(1) is used for compliance with the Section CC101.4, building energy
shall be determined by multiplying the gross conditioned floor area plus the gross semi-heated
floor area of the proposed building by an EUI selected from Table CC103.1.
Use a weighted average for mixed-use buildings.
When any compliance pathway other than Section C401.2.1 Part 1 is used for compliance with
CC101.4, building site energy use shall be determined from energy simulations.
CC103.2 Modify Section CC103.2 as follows:
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
36 | P a g e
After “approved by the code official” add “Commercial R-use buildings may comply using the
Zero Energy Buildings pathways in Appendix RC by certifying that all units meet HERS 0 or
lower with on-site renewable generation or by following the on-site renewable energy calculation
used in the Phius ZERO certification standard when following the Passive House compliance
pathway.”
CC103.3 Delete this section
CC104 Add Section CC104 as follows:
SECTION CC104 ALL ELECTRIC PATHWAY
CC104.1 General. New all-electric buildings shall comply with Sections CC101.4, CC101.5 and
with one of the following:
1) Section C401.2.1 and Section C401.4.3
2) Section C407.3 Passive House
3) Exclusively R-use buildings permitted prior to January 2024 may comply with
Section C407.4 when all dwelling units have a HERS rating of 45 or less.
CC105 Add Section CC105 as follows:
SECTION CC105 MIXED-FUEL BUILDING PATHWAY
CC105.1 General. This section together with Section CC106 establishes additional minimum
requirements for new mixed-fuel buildings.
CC105.1.1 Biomass heating. New buildings using clean biomass heating systems may
comply with this section without meeting CC105.3.1 and CC105.3.2. Buildings with any
combustion equipment using biomass that does not meet the performance standards of
clean biomass heating systems shall be deemed mixed-fuel buildings and shall comply
with this section in full.
CC105.2 On-site renewable energy. New mixed-fuel buildings shall have equipment installed
for on-site renewable energy with a rated capacity of not less than 1.5 W/ft² (16.1 W/m²)
multiplied by the sum of the gross conditioned floor area of the three largest floors.
Exception: Where the building site cannot meet the requirement in full with an on-site
renewable energy system, the building site shall install a partial system sized to not less
than 75% of the Potential Solar Zone Area.
CC105.3 Additional efficiency requirements. Additional efficiency requirements for
compliance with this Section are set forth in Sections RC105.3.1 through RC105.3.3
CC105.3.1 More efficient HVAC equipment performance. Primary heating and
cooling equipment shall meet the following efficiencies as applicable:
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
37 | P a g e
1. Space heating combustion equipment shall be rated at greater than or equal to 95
AFUE.
2. All refrigerant-based air conditioning equipment shall be a heat pump with greater than
or equal to 10 HSPF rated heating performance and greater than or equal to 16 SEER
rated cooling performance.
3. Ground source heat pump systems shall be rated at greater than or equal to 3.5 COP at
design temperature.
For multiple cooling systems, all systems shall meet or exceed the minimum efficiency
requirements in this section and collectively shall be sized to serve 100 percent of the
cooling design load. For multiple heating systems, all systems shall meet or exceed the
minimum efficiency requirements in this section and collectively shall be sized to serve
100 percent of the heating design load.
Exception:
Clean biomass heating systems used as the primary heating system.
CC105.3.2 Reduced energy use in service water-heating. The hot water system shall
meet one of the following efficiencies:
1. Greater than or equal to 82 EF combustion equipment service water-heating system.
2. Greater than or equal to 2.0 UEF electric service water-heating system.
3. Greater than or equal to 0.4 solar fraction solar water-heating system.
4. Clean biomass heating system supplied water-heating system.
CC106 Add Section CC106 as follows:
SECTION CC106 WIRING FOR FUTURE ELECTRIFICATION
CC106.1 Additional electric infrastructure. All combustion equipment and end-uses shall be
installed in accordance with this section. Capacity for the future electric circuits required in this
section shall be included in the load calculations of the original installation of electric service to
the building, and each dwelling unit for R-use buildings or portions thereof.
CC106.1.1 Electric infrastructure for dwelling and sleeping units. Combustion
equipment and end-uses serving individual dwelling units or sleeping units shall comply
with Section RC104.3 Electric Readiness.
CC106.1.2 Combustion water heating equipment. Gas-fired or oil-fired water heaters
with a capacity less than 300,000 Btu/h (88 kW) shall be installed in accordance with the
following:
1. A dedicated 208/240-volt branch circuit with a minimum capacity of 30
amps shall terminate within 3 feet (914 mm) from the water heater and be
accessible to the water heater with no obstructions. Both ends of the
branch circuit shall be labeled with the words "For Future Heat Pump
Water Heater" and be electrically isolated,
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
38 | P a g e
2. A condensate drain that is no more than 2 inches (51 mm) higher than the
base of the installed water heater and allows natural draining without
pump assistance shall be installed within 3 feet (914 mm) of the water
heater,
3. The water heater shall be installed in a space with minimum dimensions of
3 feet (914 mm) by 3 feet (914 mm) by 7 feet (2134 mm) high, and
4. The water heater shall be installed in a space with a minimum volume of
700 cubic feet (20,000 L) or the equivalent of one 16-inch (406 mm) by
24-inch (610 mm) grill to a heated space and one 8-inch (203 mm) duct of
no more than 10 feet (3048 mm) in length for cool exhaust air.
CC106.1.3 Cooking ranges, ovens and cooktops. An individual branch circuit outlet
with a minimum rating of 250-volts, 40-amperes shall be installed within three feet of
each gas or propane range or any permanently installed combustion equipment oven or
cooktop.
Exception: Commercial kitchens for cafeteria, restaurant or commercial catering
business use.
CC106.1.4 Clothes Dryers. An individual branch circuit outlet with a minimum rating of
250-volts, 30-amperes shall be installed within three feet of each gas or propane clothes
dryer.
Exception: commercial drying equipment used for manufacturing and process
loads.
CC106.1.5 Other combustion equipment. Combustion equipment not covered by
Sections CC106.1.1 and CC106.1.4 and within buildings having average ventilation at
full occupancy of 0.5 cfm/sf or less shall be provided with conduit that is continuous
between a junction box located within 3 feet (914 mm) of the appliance or equipment and
an electrical panel. The junction box, conduit and bus bar in the electrical panel shall be
rated and sized to accommodate a branch circuit with sufficient capacity for an equivalent
electric appliance, equipment or end use with an equivalent equipment capacity. The
electrical junction box and electrical panel shall have labels stating, “For future electric
equipment”.
CC106.1.6 Other combustion equipment, highly ventilated buildings. Combustion
equipment not covered by Sections CC106.1.1 and CC106.1.4 and within buildings
having average ventilation at full occupancy of greater than 0.5 cfm/sf shall comply with
Section CC106.1.6.1 through CC106.1.6.5.
CC106.1.6.1 HVAC Design and Installed Associated Electric Service. An all-
electric HVAC retrofit design shall be prepared by the HVAC engineer for
approval by the authority having jurisdiction. The electric service installed with
the building shall be sufficient to accommodate the all-electric HVAC retrofit
design. The contract documents shall show future replacement of combustion
equipment based HVAC system with an equivalent all-electric system. Contract
225 CMR 23: MASSACHUSETTS COMMERCIAL STRETCH ENERGY CODE
AND MUNICIPAL OPT-IN SPECIALIZED CODE 2023
39 | P a g e
documents shall show combustion equipment to be replaced, future electric
equipment, supporting electric, structural, and architectural infrastructure to be
installed during building construction, and space allotments for future equipment.
CC106.1.6.2 Heating, Ventilation, and Air Conditioning (HVAC)
Compatibility. HVAC design shall ensure that air, water, or other systems
serviced by combustion equipment can also be serviced by future electric retrofit
equipment without having to upgrade, alter, or update such systems.
CC106.1.6.3 Equipment Efficiencies. Electric retrofit equipment used for space
and water heating shall conform to Section C401.4.3.
CC106.1.6.4 Installed Infrastructure. Infrastructure shall be installed as part of
building construction to accommodate future electric retrofit in order to minimize
cost and disruption during retrofit. Infrastructure to be installed as part of
building construction shall include, but is not limited to, power infrastructure to
the building to accommodate future electric retrofit system, electric service to
future distributed equipment within the building, conduits to accommodate
controls to future distributed equipment within the building, and structural and
architectural elements to accommodate future retrofit equipment.
CC106.1.6.5 Space for Future Retrofit Equipment. Interior and exterior space
shall be allotted to accommodate all future electric retrofit equipment. Where
interior or exterior allotted space exceeds the space used for combustion
equipment to be replaced, and/or does not correspond to the combustion
equipment locations to be replaced, such space shall be set aside and may not be
used for any other purpose. Signage, labels, and borders shall be used to
prominently display areas and limits set aside for future equipment to prevent
encroachment.
REGULATORY AUTHORITY:
M.G.L. Ch. 25A, Sec. 6; St. 2021, Ch. 8.