School Building
Improvement and
Occupancy Plan
12 November 2020
Community updates
●School Town Halls
○July 29th
○August 5th
○September 21st
○October 29th
●School Committee meetings
●Technical report posted:
○
www.somerville.k12.ma.us/back-school-2020
Building &
Ventilation
Achieve “Low
Risk” Score
Internal
Factors
Building Assessments - Risk Management
4
June
- July
Risk Identification
Evaluate all buildings
and individual spaces
for COVID-19
transmission potential
Risk Reduction
Potential
Identify all possible
mitigation measures
& resulting
transmission
reduction
Aug
Strategy
Development
Prepare preliminary
designs, cost &
schedule estimates
Sept -
Oct
Implementation &
Phased Opening
Complete
procurement &
construction required
to attain thresholds,
and open spaces
Group ONE schools
Oct -
Nov
Ongoing
Improvements
Complete additional
construction for
remaining schools
and to improve
operations
2021
Space Planning
Identify buildings &
spaces that cannot
attain thresholds
Sept
Space Planning
Identify buildings &
spaces that cannot attain
thresholds before
December 2020
Oct
Understanding Primary Airborne Audit
Risk Assessment - Scoring System
5
1.00
1.99
2.00
2.99
3.00
4.00
Low Risk
Moderate Risk
High Risk
Air handling consistent with
ASHRAE guidelines for
aerosol spread prevention
Some air handling, but not
to reliable levels for aerosol
spread prevention
Little to no air handling,
allowing aerosol
concentration
1.00 to 1.99 = Assessment
score for opening a building
/ space for student use
Building Assessments - Deemed Unsafe During Pandemic
6
Existing
Potential
Building
Score
Risk
Score
Risk
Building system summary
Brown
3.67
High Risk
2.01
Moderate
Risk
No ventilation or central HVAC system.
Only ventilation is via operable windows.
Existing in space cooling units do not
include any filtration.
Edgerly
(CTE, NWFC)
3.08
High Risk
2.14
Moderate
Risk
No ventilation or central HVAC system.
Only ventilation is via operable windows.
Existing
High School
(1895, 1929)
3.42
High Risk
N/A
High Risk
No ventilation or central HVAC system.
Only ventilation is via operable windows.
1 = Low Risk/ASHRAE guidelines
4 = High Risk
1.0
1.5
2.0
2.5
3.0
3.5
4.0
Space & Implementation Planning
- Aligning building mitigation with academic need
Unavailable Buildings
●
Old SHS, Edgerly CTE & NWFC
classrooms, Brown School
●
Students will be placed in alternative
spaces based on SPS in-person phasing
schedule
●
Renovations to Edgerly and Brown will
be evaluated along with municipal
buildings starting in early 2021
7
Eligible Buildings
●
Evaluated mitigation logistics and best use of
each building
●
IAM estimated difficulty/schedule for each
building
●
Work must be completed on a per-building basis
●
Buildings will open in phases as mitigation work
brings buildings to Low Risk range
●
SPS determined how priority students could
occupy each building
Students may not be returning to their original school this year. Students will be brought back into
available spaces as buildings are ready, based on the SPS phased hybrid in-person plan.
Building Assessments-Group ONE Schools
8
Existing
Potential
Building
Score
Risk
Score
Risk
Building system summary
Argenziano
2.09
Moderate
Risk
1.2
Low Risk
Has good central air system to work with to
increase filtration and/or ventilation but
does not currently have any humidification.
Capuano
2.57
Moderate
Risk
1.29
Low Risk
Has good central air system to work with to
increase filtration and/or ventilation but
does not currently have any humidification.
West
Somerville
2.53
Moderate
Risk
1.52
Low Risk
Includes both central system and single
zone systems that can be modified to
increase filtration and/or ventilation but
there is no existing humidification.
1 = Low Risk/ASHRAE guidelines
4 = High Risk
1.0
1.5
2.0
2.5
3.0
3.5
4.0
Building Assessments-Group TWO Schools
9
Existing
Potential
Building
Score
Risk
Score
Risk
Building system summary
East Somerville
2.32
Moderate
Risk
1.75
Low Risk
Has good central air system to work with to
increase filtration and/or ventilation but does
not currently have any humidification.
High School
Mods
2.02
Moderate
Risk
1.49
Low Risk
Each room served by ventilation units that
include filtration and that can be improved.
1 = Low Risk/ASHRAE guidelines
4 = High Risk
1.0
1.5
2.0
2.5
3.0
3.5
4.0
Building Assessments - Group THREE Schools
10
Existing
Potential
Building
Score
Risk
Score
Risk
Building system summary
Healey
2.32
Moderate
Risk
1.56
Low Risk
Has good single zone systems in place that
can be modified to increase filtration and/or
ventilation but there is no existing
humidification.
Kennedy
School
2.69
Moderate
Risk
1.36
Low Risk
Most spaces are served by systems that
include filtration and ventilation, which can
be improved. Corridors have minimal
airflow. No humidification.
Winter Hill
2.46
Moderate
Risk
1.45
Low Risk
Most spaces are served by systems that
include filtration and ventilation, which can
be improved but there is no humidification.
Airflow pattern in classrooms can be
improved as well.
1.0
1.5
2.0
2.5
3.0
3.5
4.0
Building Assessments - New High School
11
Existing
Potential
Building
Score
Risk
Score
Risk
Building system summary
New High
School (2020)
N/A
N/A
1.2
Low Risk
New centralized system
1.0
1.5
2.0
2.5
3.0
3.5
4.0
12
School Grouping
In-Person Phase Sequence
In-Person Education
Target Start Date
Argenziano, Capuano, West
Somerville
Phases 2A & 2B:
All SPED High Needs, ELL Levels 1
& 2 (K-8)
Phase 3A: Pre-K & K
Early December 2020
New Somerville High School
Phases 2A & 2B Cont.:
ELL Levels 1 & 2 (9-12)
Next Wave/Full Circle, CTE Seniors
Early January 2021
High School Mods, East
Somerville
Phases 3B:
Grades 1 & 2
Grades 3-12 TBD
Late January 2021
Healey, Kennedy, Winter Hill
Phases 4+
TBD - March/April 2021
Building Improvement Details
●
Centralized air handling systems (based on physical constraints)
○
Increase outside air percentage
○
Increase filtration from MERV-8 to MERV-11, 13, or 14
○
Add in-line UV disinfection units
○
Add in-line humidification units
○
Update electrical and plumbing systems as needed
○
Rebalance and recommission the systems
●
Separate areas
○
Portable HEPA filters
○
Portable humidifiers
●
Nurse’s stations / Wellness rooms
○
Isolate air handling from centralized systems
○
Provide new exhaust vents to roof
●
Monitoring
○
Carbon dioxide (CO2) meters
Compressed Timeline
Current status & funding request
●
Group 1 & Group 2
○
Quotes reviewed, ready to award immediately
○
Need to proceed immediately to achieve occupancy dates
●
Group 3
○
Quotes received, anticipate award next week
●
Budget = $7.5M (Quotes + 20% contingency)
○
$3M CARES Act (must be expended by 31 Dec 2020, no City Council action)
○
$3M COVID-19 Stabilization fund (Agenda Item 39, ID # 23755)
○
$1.5M Facility Construction & Renovation Stabilization Fund (Agenda Item 40, ID # 23756)
Questions?