Engineers Connection Note:
* Install 1/4"Ø SS Tek-Screws through box frame into existing window mullion 1/8" thk. Alum. min.
with full thread diameter embedment at Three(3) Top and bottom evenly spaced with a 4" max.
side clearance with one center down each vertical side. Eight(8) Tek-Screws.
PAINT: BM "TWILIGHT ZONE” #2127-10
BM "TWILIGHT ZONE” #2127-10
BM "TWILIGHT ZONE”
#2127-10
PG: 3 of 4
Engineers General Notes
1.)
Existing sign supports are to be inspected where fasteners meets the existing wall structure.
The inspection shall verify corrosion to existing fasteners and support structure has not taken
place and document the same. If Corrosion is present, existing fasteners shall be replaced with
new equal fastener type. If the existing steel/Aluminum supports are excessively corroded,
an inspection shall be conducted to determine wall thickness prior to installation.
2.)
Murdoch Engineering confirms the existing supports fasteners/ structure is acceptable to resist
applicable loading requirements as a result of the proposed modification. The existing blade/flag
sign is equal or larger than the proposed sign total square feet. wind/Snow/Dead/Live load area.
Loading will be the same or less in proposed condition. Proposed Modification is acceptable as
loading is acceptable. It is the responsibility of the contractor/installer to verify and document all
existing conditions.
3.)
Galvanic Protection is required where dissimilar metals contact.
4.)
Install New sign box using existing fasteners or equal new equivalent.
5.)
Galvanic Protection is required where dissimilar metals contact.
Engineers Note:
As proposed Scope of work it to replace an existing with a new sign box on existing arm.
- Install new box using the existing SS hardware or replace with new equivalent hardware as needed.
- Contact Murdoch Engineering for revision due to existing field conditions / cabinet Type.
BM "TWILIGHT ZONE” #2127-10
BM "TWILIGHT ZONE” #2127-10
BM "TWILIGHT ZONE” #2127-10
PREPARED FOR:
GENERAL NOTES
PROJECT TITLE:
PROJECT ADDRESS:
murdochengineering.com
[phone removed]
2399 NJ-34 A-2
Manasquan, NJ 08736
The designs, details and specificaƟons contained in this drawing are confidenƟal. The recipients of this drawing hereby acknowledge and agree that it is the sole
property of Murdoch Engineering and that they shall neither use nor reveal any of the designs, details and specificaƟons contained in this drawing, outside of
the contractual agreement expressed wriƩen permission from Murdoch Engineering.
DeviaƟons from this drawing shall not be made without consulƟng Murdoch Engineering. In case of incongruiƟes between drawings, specificaƟons, and details
included in contract documents, Murdoch Engineering shall decide which indicaƟon must be followed and their decision shall be final.
Copyright Murdoch Engineering.
All rights reserved.
GENERAL:
1.
2.
3.
4.
ALL MATERIALS AND WORK SHALL CONFORM TO THE REQUIREMENTS OF THE APPLICABLE LOCAL BUILDING
CODE.
CONSTRUCTION METHODS AND PROJECT SAFETY: DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE AND DO NOT INDICATE METHODS, PROCEDURES, OR SEQUENCE OF CONSTRUCTION. TAKE
NECESSARY PRECAUTIONS TO MAINTAIN AND ENSURE THE INTEGRITY OF THE STRUCTURE DURING
CONSTRUCTION. THE EOR WILL NOT ENFORCE SAFETY MEASURES OR REGULATIONS. THE CONTRACTOR
SHALL DESIGN, CONSTRUCT, AND MAINTAIN ALL SAFETY DEVICES AND SHALL BE SOLELY RESPONSIBLE FOR
CONFORMING TO ALL LOCAL, STATE, AND FEDERAL SAFETY AND HEALTH STANDARDS, LAWS, AND
REGULATIONS.
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND SITE CONDITIONS PRIOR TO THE START
OF CONSTRUCTION AND NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR INCONSISTENCIES
THAT ARE FOUND. NOTED DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE
DRAWINGS.
ALL OMISSIONS AND/OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE WORKING DRAWINGS AND
SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND FIELD INSPECTOR. THE
ENGINEER SHALL PROVIDE A SOLUTION PRIOR TO PROCEEDING WITH ANY WORK AFFECTED BY THE CONFLICT
OR OMISSION.
5. WHERE NO CONSTRUCTION DETAILS ARE SHOWN OR NOTED FOR ANY PART OF THE WORK, CONSTRUCT IN
ACCORDANCE WITH THE STEEL CONSTRUCTION MANUAL, 14TH EDITION OR 2010 ALUMINUM DESIGN
MANUAL .
6. WHEN A DETAIL IS IDENTIFIED AS TYPICAL, THE CONTRACTOR IS TO APPLY THIS DETAIL IN ESTIMATING
AND CONSTRUCTION TO EVERY LIKE CONDITION WHETHER OR NOT THE REFERENCE IS REPEATED IN EVERY
INSTANCE.
7. ANY CHANGE TO THE DESIGN AS SHOWN ON THE DRAWINGS REQUIRES PRIOR WRITTEN APPROVAL FROM
DESIGN ENGINEER OF RECORD BEFORE CONSTRUCTION.
8. WORK PERFORMED IN CONFLICT WITH THE STRUCTURAL DRAWINGS OR APPLICABLE BUILDING CODE
REQUIREMENTS SHALL BE CORRECTED AT THE EXPENSE OF THE CONTRACTOR.
9. VERIFICATION: VERIFY ALL DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS BEFORE STARTING WORK.
NOTIFY THE EOR IMMEDIATELY OF ANY DISCREPANCIES.
STEEL
1. STEEL SHAPES SHALL CONFORM TO THE FOLLOWING:
Fy=42 KSI MIN.
Fy=46 KSI MIN.
Fy=55 KSI MIN.
Fy=36 KSI MIN.
ROUND HSS
SQUARE/RECT HSS
THREADED ROD
STEEL PLATE STD.
PIPE
ASTM A500, GR B
ASTM A500, GR B
F1554 GR 55
ASTM A36 ASTM
A53, GR B
Fy=35 KSI MIN.
2. BOLTS SHALL CONFORM TO ASTM A325 UNO.
3. BOLTS AND THREADED ROD SHALL BE HOT-DIP GALVANIZED PER ASTM F2329 UNO.
4. ANCHOR BOLTS SHALL CONFORM TO ASTM F1554 UNO.
5. NUTS SHALL CONFORM TO ASTM A563.
6. WASHERS SHALL CONFORM TO ASTM F844.
7. STEEL HARDWARE SHALL BE HOT-DIP GALVANIZED PER ASTM A153 UNO
8. WELDING:
a. WELD STRUCTURAL STEEL IN COMPLIANCE WITH ANSI/AWS D1.1 AND AISC SPECIFICATION, CHAPTER
J. WELDERS SHALL BE CERTIFIED AS REQUIRED BY GOVERNING CODE AUTHORITY. WELDING SHALL
BE DONE BY ELECTRIC ARC PROCESS USING LOW-HYDROGEN ELECTRODES WITH SPECIFIED TENSILE
STRENGTH NOT LESS THAN 70 KSI UNLESS NOTED OTHERWISE.
b. ALL SHOP AND FIELD WELDS SHALL BE PERFORMED BY AN AWS OR ICC CERTIFIED WELDER WITH
ACTIVE STATUS AT TIME OF WELDING
c. UNLESS A LARGER WELD SIZE IS INDICATED, PROVIDE MINIMUM SIZE WELDS PER
AISC SPECIFICATION, SECTION J2, TABLE J2.4
d. BASE PLATES SHALL BE WELDED ON TOP AND BOTTOM WITH CONTINUOUS WELDS
OF AT LEAST 1/4" (IF PLATE IS CUT TO FIT TUBE INTO PLATE)
1. FABRICATE AND ERECT ALUMINUM IN COMPLIANCE WITH THE ALUMINUM ASSOCIATION (AA) 2010
ALUMINUM DESIGN MANUAL (ADM) 1, THE SPECIFICATIONS FOR ALUMINUM SHEET METAL WORK
(ASM35), AND IBC CHAPTER 20.
2.
3.
4.
PIPE AND TUBE SHALL BE 6061-T6 PER ASTM B241 OR B429 WITH Ftu=38 KSI MIN, Fty=35 KSI MIN, Ftuw=24
KSI MIN, Ftyw=15 KSI MIN.
STD STRUCTURAL PROFILES SHALL BE 6061-T6 PER B308 WITH Ftu=38 KSI MIN, Fty=35 KSI MIN, Ftuw=24
KSI MIN, Ftyw=15 KSI MIN.
SHEET AND PLATE SHALL BE 6061-T6 PER ASTM B209 WITH
Ftu=42 KSI MIN, Fty=35 KSI MIN, Ftuw=24 KSI MIN, Ftyw=15 KSI MIN.
5.
6.
7.
EXTRUSIONS SHALL BE 6061-T6 PER ASTM B241 OR B429 WITH Ftu=38 KSI MIN, Fty=35 KSI MIN, Ftuw=24 KSI
MIN, Ftyw=15 KSI MIN.
ALL SHOP AND FIELD WELDS SHALL BE PERFORMED BY AN AWS OR ICC CERTIFIED WELDER WITH
CURRENT STATUS AT TIME OF WELDING
UNLESS A LARGER WELD SIZE IS INDICATED, PROVIDE MINIMUM SIZE WELD PER ADM. ALL ALUMINUM
WELDED JOINTS SHALL HAVE WELD SIZES OF AT LEAST 14 INCH
ALUMINUM:
8. FILLET WELDS SHALL NOT EXCEED THINNEST MEMBER WALL THICKNESS JOINED.
9. ALUMINUM WELD FILLER SHALL BE 5356 ALLOY
10.WELDING PROCESS GMAW OR GTAW SHALL BE IN ACCORDANCE WITH AWS D1.2
11.ALUMINUM CHANNEL LETTERS SHALL BE CONSTRUCTED OF 0.090" RETURNS AND 0.125" BACKS
MINIMUM, UNLESS A LARGER SIZE IS INDICATED ON DRAWINGS. THIS NOTE SHALL SUPERCEDE
DRAWING DETAILS.
12.PROVIDE NEOPRENE GASKET BETWEEN DISSIMILAR METALS TO PREVENT GALVANIC CORROSION
13.ALUMINUM DIRECTLY EMBEDDED INTO CONCRETE SHALL BE CAPPED AT BOTTOM AND COATED WITH
BITUMINOUS COATING OR POLYURETHANE WHERE IN CONTACT WITH CONCRETE.
14.FASTENERS BETWEEN DISSIMILAR METALS SHALL BE STAINLESS STEEL 316.
EXISTING CONDITIONS:
1. IF EXISTING CONDITIONS ARE NOT AS DETAILED IN THIS DESIGN, THE INSTALLER SHALL CEASE WORK
AND NOTIFY MURDOCH ENGINEERING IMMEDIATELY.
2.
3.
4.
MURDOCH ENGINEERING WILL NOT BE PERFORMING ON-SITE INSPECTIONS OR VERIFICATIONS. IT IS THE
RESPONSIBILITY OF THE INSTALLER, STRUCTURE OWNER, AND PROPERTY OWNER TO IDENTIFY EXISTING
CONDITIONS AND CONTACT MURDOCH ENGINEERING WITH ANY DISCREPANCIES OR CONCERNS.
INSTALLER SHALL CONFIRM THE DIAMETER AND THICKNESS OF EXISTING MEMBERS AND NOTIFY
MURDOCH ENGINEERING OF ANY DISCREPANCIES.
INSTALLER SHALL INSPECT AND CONFIRM THE QUALITY OF EXISTING STRUCTURE AS "IN GOOD REPAIR". IF
THERE ARE ANY INDICATIONS THAT THIS IS NOT THE CASE, INSTALLER SHALL CEASE WORK IMMEDIATELY
AND NOTIFY MURDOCH ENGINEERING.
5. ANY EXISTING INFORMATION SHOWN HAS BEEN FURNISHED BY THE PERSON(S) OR COMPANY THIS
DOCUMENT WAS PREPARED FOR
(SEE TITLE BLOCK). MURDOCH ENGINEERING IN NO WAY CERTIFIES THIS INFORMATION AS "AS-BUILT".
IF THERE IS ANY REASON TO BELIEVE THE EXISTING CONDITIONS DETAILED HEREIN ARE NOT ACCURATE,
MURDOCH ENGINEERING SHALL BE NOTIFIED IMMEDIATELY.
SCOPE OF WORK:
1. LIMITS OF LIABILITY TO EXTEND ONLY TO THE QUANTITY INDICATED. ATTEMPTS IN PART
OR IN WHOLE TO INSTALL GREATER QUANTITIES THAN THOSE SPECIFIED WITHOUT
CONSULTING MURDOCH ENGINEERING SHALL VOID ALL PROFESSIONAL LIABILITY
AND COVERAGE. ENGINEERING LIABILITY IS LIMITED TO BUILDING CONNECTIONS.