Matters ▸ Attachment
20241022_SS Report_Digital — File 26-0826
Legalizing Mid-Rise Single-Stair
Housing in Massachusetts
A Report on the Impact of Allowing Mid-Rise
Point Access Blocks on Housing Design and
Development in Greater Boston and Beyond
October 2024
Legalizing Mid-Rise Single-Stair Housing
in Massachusetts
A Report on the Impact of Allowing Mid-
Rise Point Access Blocks on Housing
Design and Development in Greater Boston
and Beyond
October 2024
Foreword by
Luc Schuster, Boston Indicators
Report by Utile
Sam Naylor
Tim Love
Simona Rodriguez Villand
Camille Wimpe
Kyle Jonasen
Aaron Smithson
Lilly Saniel-Banrey
Maria Ferreria
Editorial Advising by The Joint Center for
Housing Studies of Harvard University
Chris Herbert
Carlos Martín
Alexander Hermann
David Luberoff
Consulting, Advice, and Support from
AIA Massachusetts
Boston Society for Architecture
Code Red Consulting
Conrad Speckert, LGA Architectural Partners
Eduardo Mendoza, Livable Communities
Initiative
Michael Eliason, Larch Lab
Sean Jursnick, SAR+ Architects
Stephen Smith, Center for Building in North
America
©2024 President and Fellows of Harvard College.
Any opinions expressed in this report are those
of the author(s) and not those of the Joint Center
for Housing Studies of Harvard University,
Boston Indicators, or of any of the persons
or organizations providing support to these
organizations. This report was made possible
with funding from Boston Indicators, the research
center at the Boston Foundation.
The material provided in this report is for
informational purposes only. The authors,
funders, and other contributors assume no
liability for any damage, injury, loss, or expense
that may be incurred or suffered as a result of the
use of this report, including products, building
techniques, or practices. Drawings and diagrams
of projects have been made with every effort
to illustrate the work accurately. The editors
apologize for any errors or misrepresentations.
Boston Indicators is the research center at the
Boston Foundation, which works to advance a
thriving Greater Boston for all residents across
all neighborhoods. We do this by analyzing key
indicators of well-being and by researching
promising ideas for making our region more
prosperous, equitable and just. To ensure that
our work informs active efforts to improve our
city, we work in partnership with community
groups, civic leaders, and Boston’s civic data
community to produce special reports and host
public convenings.
bostonindicators.org
The Harvard Joint Center for Housing Studies
strives to improve equitable access to decent,
affordable homes in thriving communities. We
conduct rigorous research to advance policy
and practice, and we bring together diverse
stakeholders to spark new ideas for addressing
housing challenges. Through teaching and
fellowships, we mentor and inspire the next
generation of housing leaders.
jchs.harvard.edu
Utile is a Boston-based design firm built like
a think tank. We thrive on solving complex
problems in intelligent and pragmatic ways.
From theoretical issues that frame policy to
the practical implementation of architectural
commissions, Utile develops a rigorous research-
based approach for finding the best solutions.
utiledesign.com
CONTENTS
Foreword
5
I.
Status Quo vs. Single-Stair
6
Podium Production
6
Point Access Blocks
8
Quality of Life
10
Unlocking Density
14
II.
Greater Boston Housing History
16
Resilient Residential Types
16
An evolving Bulding Code
18
Single Stair Today
20
III.
Egress Code Landscape
22
The North American Outlier
22
A Changing Landscape
25
The Proposal
27
Related Building Code Provisions
Worth Reconsideration
28
IV.
Point Loaded Potentials
30
Building More Mid-rise
30
PABs for Small Plots
30
Homes We Can be Proud of
32
Citations
36
Terms
37
Resources
38
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
4
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
FOREWORD
We talk often about Greater
Boston’s housing situation as a
crisis. The better description is that
it’s become chronically ill. But not
terminally. We need to bring to bear
all the remedies we can to treat the
mix of symptoms that deprive our
housing market—and by extension,
our communities—of full health.
Full health would be having an
abundant offering of diverse
housing types so that families at
different stages of life can find
suitable housing. Instead, we have:
• Underproduction compared to
high demand for people to live
and work in the area
• Rising home prices and rents
• Lack of diversity in housing
types, without enough lower-cost
options, especially in walkable,
transit-proximate urban areas
• Insufficient family-sized units in
high-demand areas
• Sprawling development
patterns, which isn’t good for
environmental sustainability or
for quality of life
• Apartment complexes with
restricted layouts that often lack
community-enhancing common
spaces
Boston Indicators (and many,
many others) has been exploring
the role of zoning restrictions in
contributing to this housing market
dysfunction through research
projects like Zoned Out and
Exclusionary by Design. And the
state government is starting to
act in a new way, as evidenced by
2021’s MBTA Communities law and
the recent statewide legalization
of Accessory Dwelling Units in
the Affordable Homes Act. But
there’s a growing recognition that
zoning reform alone won’t cure
all our housing ills. It can certainly
create an onramp for more, and
better, housing construction.
But it’s clear we need to work on
other fronts as well. So, with this
report, we begin an exploration
of other barriers to creating the
abundant, diverse, affordable
housing that we all deserve.
Looming large among them is the
building code. It is an amalgam
of regulations that should evolve
with time and technology. But old
concerns and considerations live
on in the building code long after
technological or architectural
advances have overridden their
safety value. For example, the
use of engineered wood is often
limited or prohibited in buildings
of a certain height, even though
other countries have proven its
flexibility to achieve the same fire
ratings as concrete or steel with far
less weight and carbon footprint.
Regulations requiring unnecessarily
large and expensive elevators
are another area starting to get
scrutiny.
But here we start by diving into
staircases and the common
building code requirement that
projects between three and six
stories include two separate means
of egress (i.e., staircases). As the
fire safety that redundant staircases
provide has become more than
matched by advances in materials,
smoke detection, and sprinkler
systems, we’ve seen growing
momentum across North America
to reconsider this requirement.
So, in this report we explore the
reasons for, and potential impact
of changing this requirement
in Massachusetts. Such a shift
might allow a huge jump in unit
design flexibility. It’s especially
relevant in Greater Boston as
housing advocates are working
to direct housing production into
dense walkable neighborhoods
near transit. These areas tend to
be more built-out and parcels are
typically smaller. So, allowing for
single-stair construction unlocks
these parcels for developments
that fit their scale, and pencil out—
potentially doubling the number of
units permissible.
We could have no better partners
in this work than Harvard’s Joint
Center for Housing Studies and
Utile Design—the former a leading
national think tank on all things
housing, and the latter an innovative
architectural and planning firm
that blends design capability
with broader policy and planning
expertise. Their skills combined
made this unique report possible,
creating a primer for the growing
conversation around revising the
building code in Massachusetts.
While it doesn’t address every
detail that will inevitably emerge,
we hope it’s a useful starting point
for discussions around balancing
safety concerns with the urgent
need to allow for the construction of
more flexible, affordable housing in
Massachusetts.
—Luc Schuster, Boston Indicators
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
5
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo vs. Single-Stair
Building codes, as much as
municipal-level zoning codes,
affect the geographic distribution,
physical characteristics, and market
dynamics of housing production.
Yet, because knowledge of building
codes is the purview of architects
and builders and not economists or
policymakers, the impact of building
codes is underappreciated in the
housing policy or planning world.
Similarly, because knowledge
of the building code’s impacts
on development and design is
only gained by spending years
in practice, their significance
for architectural design is under
considered as a real area of
innovation in design schools. One
pernicious example is the double-
loaded podium building, which
has arisen from the intersection
of egress codes, construction
types, and market logics, creating
a housing type that has been
much-maligned in the media, and
yet continues to be the dominant
multifamily typology across much of
the US.
A podium building—sometimes
referred to as a five-over-one
because it often consists of five
wood-framed stories built atop a
“podium” of one story of concrete
or steel—can maximize value
in two ways. The first is the way
these buildings push density to
the maximum just below the high-
rise building code threshold, often
demarcated as the point at which
fire rescue service ladders from
the ground can no longer reach the
highest occupiable window. (This is
defined in the International Building
Code (IBC) as 75 feet above grade
plane, but in Massachusetts has
been amended to be 70 feet.)
This is important because the
structural framing that can be
PODIUM PRODUCTION
Double-Loaded Podium Building
50-70’
<70’
L1
Light-Wood
(Type III-V)
Concrete or Steel
(Type I-II)
L2
L3
L4
L5
L6
Min. Exit Seperation
> 1/3 Building Diagonal
Dead End
Max. 50’
Typ. 12-15’
Typ. 10-11’
100-636’
Unit
Podium
Building Section
Typical Floor Plan
Axonometric
6
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
used for non-high-rise buildings,
which includes light wood frame
and lightweight steel construction,
is much less expensive than the
noncombustible steel frame or
cast-in-place concrete structural
solutions required by the high-rise
code. Other secondary life safety
requirements kick in too, that in
aggregate with the added costs
of the structural frame can add
between 15% and 25% to the cost
of the project on a per square
foot basis.1
If these parameters explain the
height of cost effective multifamily
buildings, the cost of vertical
circulation (stairs and elevators)
helps explain the size of typical
five-over-one buildings in plan. In
North America, a typical multifamily
building has two fire stairs and one
or two elevators (depending on the
size of the building and the specific
market conditions). Since most
buildings are required to have two
stairs connected by a smoke-proof
and fire-rated corridor, developers
are incentivised to stretch the floor
plan of said building to maximize
the number of units on either
side of the hallway (or a so-called
double-loaded corridor) while
remaining within the limitations for
travel distances from the furthest
point in the most remote unit from
an exit. Put another way, real
estate developers prefer project
opportunities where they can
harvest as much net rentable or
sellable residential area as possible
from an investment in two stairs and
two elevators. This is called building
efficiency (net area divided by
gross area), and usually calculated
as a percentage figure, ranging
from 75% to 90% in multifamily
structures. This translates to
typical residential floor plates that
need to be at least 14,000 gross
square feet to meet financing
underwriting requirements in
most North American markets. In
locating these projects, sites are
primarily chosen by how best a
double-loaded podium building
can be fit within it, or stretched to
fill its volume. Not only is this the
most efficient building to produce
under the confluence of our codes
and construction types, but it’s
also always more efficient to build
one large building than two smaller
ones as the latter would duplicate
the required number of stairs,
and greatly expand the building
services and exterior wall area,
limiting efficiency. Because of this,
and because developments are
naturally more profitable as
they grow (any building above a
handful of units requires the same
consultants, code complexities,
and construction sophistication as
a building with hundreds of units),
the logic of the podium building
then is also baked into higher land
prices, regardless of present zoning
requirements. Thus sites that are
too small for these building types
are either combined into a larger
parcel, or lay underdeveloped.
When combined with the rationale
for building heights described
above and other factors, the six (or
seven in some cases) story I-, H-,
L- and C-shaped double-loaded
podium building is both justified
and elevated as a model to emulate,
without equal.
Typical Greater Boston Double-loaded
Podium Footprints
Six-plex
Footprint on
Median Sized
Boston Parcel
(4,600 SF)
26K
12K
12K
9K
21K
61K Footprint
29K
31K
20K
55K
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
7
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
POINT ACCESS BLOCKS
The primary reason behind the
ubiquity of podium buildings is
the requirement for two means
of egress (stairs) for any building
above 12 units (in Massachusetts).
This limitation arose in the mid-
20th century in North America,
but it is not common worldwide.
Data shows that advances in
construction technology, both
passive and active, and other life
safety provisions make the two-
stairway requirement antiquated,
and unreasonable for small mid-
rise buildings that can offer equal
or greater life safety provisions
within an architectural typology
that offers more efficiency, daylight,
ventilation, and variations
in density.
Single-stair residential buildings,
or what are commonly referred to
as Point Access Blocks (PABs),
compose a collection of building
types where, in lieu of a corridor
loaded on both sides with units,
units radiate from a single central
vertical circulation core. With only
one stair access point there is no
need for a long, dimly lit interior
hallway, and thus more floor space
can be dedicated to units, and
those units can be more flexible
in shape, size, and location. This
type can also be ganged together
to create larger complexes, ones
that offer similar efficiencies in
plan but far superior quality of light
and air for the residents. In Boston
and across North American cities
that expanded in the mid-20th
century there is a history of PABs,
often modeled after international
precedents at the time. Today,
across the world, the dominant
form of multifamily housing
continues to be the PAB, except
for North America.
Small Infill
52'
27'
70’
77’
43'
24'
Capitol Core
Seattle, WA
2017
17 Units
76% Efficient
1,374 GSF Floor Plate
Apartment in Katayama
Suita-Shi, Japan
2007
10 Units
66% Efficient
970 GSF FP
Party Wall
110 Rooms
Barcelona, Spain
2016
22 Units
88% Efficient
+/- 3,030 GSF FP
88'
40'
66’
72’
68'
42'
17 Apartments
Paris, France
2017
17 Units
84% Efficient
+/- 2,300 GSF FP
Side / Single-Loaded
John Street
Seattle, WA
2016
25 Units
83% Efficient
4,380 GSF FP
116'
64’
58’
45'
81'
32'
8
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
High Street Apartments
Thornbury, Australia
2022
13 Units
83% Efficient
2,225 GSF FP
Center Core
84’
44’
46’
74'
76'
68'
81'
51'
37'
Quartier am Seebogen
Vienna, Austria
2021
49 Units
83% Efficient
5,713 GSF FP
Suurstoffi Development
Zurich, Switzerland
2015
16 Units
90% Efficient
3,455 GSF FP
Apartments in Wetzikon
Wetzikon, Switzerland
2021
12 Units
89% Efficient
2,891 GSF FP
Blocks
68’
70’
39'
88'
250'
51'
128'
88'
288'
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
9
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
Fittjahojden
Stockholm, Sweden
2019
24 Units per core
88% Efficient
3,480 GSF FP
Dennewitz Eins
Berlin, Germany
2013
12-18 Units per core
88% Efficient
+/- 4,070 GSF FP
Without the requirement of two
stairs, units in PABs can be
arranged in a variety of ways
around or next to a vertical
circulation armature. In a double-
loaded building, the only units that
have dual aspect (access to more
than one direction of exterior wall
face) are on the ends or corners.
In PABs, with the removal of a
connective hallway, many more
units have opportunities for direct
sunlight and cross ventilation.
If only half of units in a double-
loaded building have access to
direct sunlight (because they have
windows on only one solar aspect),
almost all units in a PAB can have
access (because of the possibility
for dual aspect units). More direct
sunlight is better for passive solar
gain, and more natural daylight on
any facade means bedrooms are
possible; making units more livable,
sustainable, and family oriented.
Cross ventilation, key to moving
fresh air through a unit, or expelling
hot air and bringing in cool air in
the summer make it more likely
residents use operable windows
to improve indoor air quality
and comfort in the least energy
intensive method.
QUALITY OF LIFE
N
W
E
S
Single-Aspect
Dual-Aspect
Triple-Aspect
60’
60’
50’
Double-Loaded
Floor Plan
16,000 GSF Floor Plate
20 Units
88% Efficient
Point-Loaded
Floor Plan
16,000 GSF FP
16 Units
91% Efficient
10
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
More windows means the
opportunity for more bedrooms
and thus more family-sized
units. Increasing these units in
multifamily housing production
is key to creating buildings and
neighborhoods that people can
and want to live in for their entire
lives. Double-loaded buildings
disincentive these types of units. In
Boston-area market-rate buildings,
the typical ratio of units often
amounts to a mix of 20 – 25%
studios, 50% one-bedrooms, 20 –
25% two-bedrooms, and 5% three-
bedroom units. Units with four, five,
or more bedrooms are extremely
rare, and three-bedroom units are
reserved for end or corner units
(which have more exterior window
opportunities), making them
naturally more expensive and less
financially accessible to prospective
buyers or renters. One reason for
this deficit can be attributed to the
geometry of the double-loaded
floor plan. The connective hallway
between the two stairs creates a
fixed building depth (the hallway
cannot be broken), and since every
bedroom needs an exterior window
by code, the only way to expand a
unit’s size is lengthwise.
24-34'
Dark
Interior
Section
S
20-70'
Limited
Air Flow
Double-Loaded
Unit Plan
Key Building Plans
3 Bed / 2 Bath
Single-Aspect
3 Bed / 2 Bath
Dual-Aspect
Unit Sections
Point-Loaded
Unit Plan
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
11
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
Growing linearly results in a
proportional increase of the area
without natural light. This darkened
area then has less usefulness to
a unit, and the resultant rental
increase from its larger square
footage is rarely justified fiscally or
formally. PABs on the other hand,
can essentially be buildings of
only corner or end units, greatly
increasing the flexibility of unit
design to increase access to
sunlight and cross ventilation, but
also other spatial arrangements as
well. PABs also incentivise family
units, both because of their higher
efficiency at smaller floor plates
and the fact that, under proposed
code reforms, any one single-stair
building has a fixed number of
units per floor, which encourages
enlarging units rather than adding
more smaller ones. While PABs
might have fewer total units per
floor plate when compared to a
double-loaded construction, these
units are typically larger, more
diverse in layout, have more access
to natural light and air, and are in
compact buildings that otherwise
would not pencil out on small to
medium sized parcels.
29'
29'
29'
31'
22'
24'
34'
45'
29'
27'
49'
29'
1
2
2
3
3
1
1
2
1
1
Double-Loaded
Unit Plans
Key Building Plans
612 SF
1 Bed / 1 Bath
560 SF
1 Bed / 1 Bath
900 SF
2 Bed / 1 Bath
705 SF
2 Bed / 1 Bath
1,182 SF
3 Bed / 2 Bath
Point-Loaded
Unit Plans
1,054 SF
3 Bed / 2 Bath
12
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
The central circulation core of a
PAB also increases its opportunities
for beauty and socialization. In a
double-loaded building the endcap
units, while hyper valuable, result
in dim and often interminably
long interior corridors. These
hallways, rarely naturally lit, hurt
the development pro-forma, and
do no service to the residential
design of one’s front door. PABs
without the need for a corridor
are opened up to spending more
money on the design of one single
stair to be both more pleasant
an experience and compact a
pathway to one’s home. In surveyed
projects natural light was more
prevalent in these types, either
from the stairway’s being pushed
to the side of a building, or being
placed between two volumes with
a light well in between. The single
stair (and often elevator), is also
part of a sequence of circulation
that everyone must pass through
and by which residents might
run into neighbors more often.
In buildings under this proposal,
which would be permitted to have
20 units served by a single stair on
the five upper stories (as opposed
to over a hundred in the typical
podium building), social cohesion
of residents and neighbors can be
imagined in greater clarity when the
journey from the street to one’s sofa
is bright and compact rather than
boring and claustrophobic.
Boston
Boston
Boston
Australia
Switzerland
Switzerland
Netherlands
Australia
Argentina
Australia
Australia
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
13
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
In Greater Boston,2 very few units
are created in buildings with more
than nine but fewer than 30 units. A
key to understanding this outcome
is that buildings above 12 units or
more than three stories require two
means of egress.3 While double-
loaded buildings provide high
efficiency at larger footprints, they
suffer greatly on small to medium
sized parcels. Thus, those sites
remain underdeveloped, or lie in
wait to be bought and aggregated
into larger parcels which are
more suitable for a podium style
development scheme. Greater
Boston cannot wait for those
aggregations, and shouldn’t settle
for only one scale of mid-rise
housing. PABs are well suited to
small and medium scale parcels,
and with one less stair, and way
less hallway, can achieve much
higher floor plan efficiencies than
their double-loaded counterparts.
New England’s old city fabrics have
a multitude of parcels at this smaller
scale, often on existing transit-
friendly squares and streets that are
primed for more development, but,
without a change to the building
code, remain unprofitable to
develop as such.
On a typical six-plex Boston parcel,
which ranges from 3,000 – 5,000
square feet (the most common
parcels in size in Greater Boston),
a double-loaded building is 10%
less efficient than a similarly sized
single-stair building. The extra stair
and attendant hallway accounts
for around 280 square feet, or 10%
of the total floor area. This can
account for equally 10% or more
of the total construction cost of a
project (anywhere from $200,000
to $500,000),4 and considering
that the same area is rentable in
UNLOCKING DENSITY
Total Housing Units Built in Greater Boston
by Number of Units in the Building (2001 – 2022)
Number of Units Built
Single-Stair Limit
Article 80 SPR Limit
Boston IDP Limit
Number of Units in Building
0
2,000
4,000
6,000
8,000
10,000
12,000
14,000
16,000
3-5
6-9
10-12
13-16
17-20
21-30
31-50
51-100
101-150
151-300
301+
Greater Boston study
area, defined as the
MBTA Rapid Transit
Communities
Min.
Exit
Sepe-
ration
48’
60'
85'
Median Parcel Size in Greater Boston (4,600 SF)
54'
Unit
Small Double-Loaded Plan
82% Efficient
Small Single-Stair Plan
92% Efficient
2,880 GSF Floor Plate
3 Units
2,880 GSF FP
3 Units
14
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
a single-stair building, it could
represent an even greater hit to
the pro-forma. The cost is enough
to break most budgets and make
these kinds of sites unbuildable in
the current market.
Single-stair mid-rise PABs can
fit into these sites right now, and
have a circulation armature which
allows for massings to be broken
up; which could also break down
the notoriety of new development.
The narrative of any new housing,
when talked about in community
meetings or elsewhere online,
evokes for many the image of a
bulking and characterless podium-
style building of uniform height,
shape, and facade. The necessity
to connect two stairs, both in
plan with an efficient corridor,
and in section, so that every unit
can access both stairs, results in
architectural designs unable to
modulate their massings beyond
minor moves of a few feet. PABs
on the other hand, which have no
hallway and are limited in floor plate
size, can be clustered together in
arrangements that can step up,
down, or laterally—differentiating
their urban form in more meaningful
ways. The allowance of a single
stair is critical to achieving the kind
of urban variety that our cities need
and that the public deserves but,
without a change to the building
code, will be only seen abroad or in
unrealized designs not yet subject
to the realities of market-driven
housing production.
Through-block
Connections
Variable Floor
Heights
Podium Consistency
Hallway Prevents
Deeper Setbacks
Mid-Rise Double-Loaded Podium
Limited Massing Options
Mid-Rise PABs in Sequence
Variable Massing Possible
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
15
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
II. Greater Boston Housing History
Most of Boston’s best-known
housing typologies, such as the
triple-decker, Back Bay rowhouse,
or Fenway brick apartment houses,
also originated from market logics
and construction constraints of
their day. The triple-decker is a
useful case study because, like
the five-over-one, the building
type resulted from a confluence
of several technical, regulatory,
and market factors. When waves
of newcomers, including Irish and
Eastern European immigrants,
arrived in Boston in the late 19th
century, and expanded streetcar
networks made longer distance
commuting more feasible for
the lower middle class, vast new
areas in Dorchester and Roxbury
were developed as residential
neighborhoods. Given the relatively
low land values and the need to
build new housing quickly and
cheaply, a novel housing type was
developed that didn’t require semi-
skilled masons or the dimensional
precision necessary for zero-lot-
line rowhouses, the preferred
typology of central Boston for the
middle and upper classes. The
answer was a free-standing wood
frame three-story building with a
different family living on each floor:
the triple-decker. The maximum
number of stories of the triple-
decker was fixed by the maximum
standard length of mass produced
lumber as the result of recent
industrial technologies. Balloon
framing, a construction innovation
that took advantage of these new
lightweight and more precisely cut
framing components, meant that
structures could be assembled
very quickly by unskilled labor.
Housing production was further
accelerated when developers could
sequence construction trades
crews across dozens of parcels.
RESILIENT RESIDENTIAL TYPES
627 – 629 Commonwealth Ave.
Boston, MA
Stories
4
Built
1908
728 Commonwealth Ave.
Boston, MA
Stories
5
Built
1912
842 – 864 Massachusetts Ave.
Cambridge, MA
Stories
3 – 5
Built
1925
16
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
This market flexibility, coupled
with the optimization of land use
and construction efficiency meant
that the triple-decker was the most
common multifamily residential
building type built in New England
cities from the 1880s until the 1930s.
While the triple-decker now
represents a cherished part of the
urban fabric, at the time it was
simply the most efficient means
of housing the most people at the
least cost in the shortest time.
Today that product is the podium
building, and, while its cultural
relevance remains to be seen,
its inflexibility to fit into the fine
grain urbanism of the region has
left many communities wary of
any new development, affordable
or not. Similarly, this form is less
conductive to fitting on parcels
within the fine-grain urban fabric in
Massachusetts, as demonstrated in
fewer new housing units per capita
when compared to other states.5
Single-stair buildings here have, to
varying degrees, been permitted
for most of the 20th century up to
the mid-1970s. A survey of these
types reveals the pervasiveness
of existing mid-rise, and in some
cases high-rise housing. Many
Bostonians live in single-stair
buildings, and their relative
compactness (in contrast to podium
buildings today), has shaped an
urban fabric that can support
walkable and transit oriented life.
If the city’s own past is any lesson,
and if international precedents can
be instructive, single-stair mid-rise
buildings might be deemed as the
triple-(or more)-decker of the future.
24 Highland Ave.
Cambridge, MA
Stories
5
Built
1950
1350 Massachusetts Ave.
Cambridge, MA
Stories
5 – 22
Built
1964
1105 Massachusetts Ave.
Cambridge, MA
Stories
13 (Scissor Stair)
Built
1970
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
17
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
AN EVOLVING BULDING CODE
In 1630 Boston outlawed the building
of wooden chimneys and thatched
roofs, creating what is now understood
as the first formal building code in the
US. Boston grew its own code over the
years, and it became a model code for
surrounding towns and cities as well.
In 1974 the Commonwealth created
the first statewide code (first edition),
which has evolved but remained
under the state’s purview until today;
cities must follow it and cannot make
regulations that are more permissive
than what the state regulates. The
current edition (ninth) of the state code
is an amended version of the model
International Building Code (IBC) 2015
code, and was adopted in 2017 by
Massachusetts. In late 2024 the state
will formally adopt the 2021 IBC under
the new tenth edition of the code. The
IBC is the most commonly used model
code countrywide; however, each
state and some cities adopt different
versions, with Vermont and Georgia
adopting parts of the National Fire
Protection Association (NFPA) code in
lieu of IBC for the sections pertaining to
the number of means of egress.6
Throughout the time when Boston had
its own building code, single and dual
egress requirements varied. Despite
references to the requirement for two
means of egress dating as far back as
1803, single-stair residential buildings
were built of varying heights up to the
mid-20th century. During some periods
the code allowed one to egress through
Timeline of the Boston
Building Code
1630
City of Boston is officially founded.
1760
The Great Boston Fire destroyed
349 buildings displacing thousands
of people.
1871
The city’s first Building Department
was established by Chapter 280 of
the Acts of 1871.
1872
The Great Boston Fire destroyed 65
acres of buildings.
1873
(S. 44) “Every building must have a
fire means of escape approved by
the inspector of buildings.”
1895
(S. 81) “Every building occupied
by two or more families, shall have
one or more safe means of egress,
satisfactory to said commissioner.”
1901
(S. 82) “Buildings two stories or
more shall provide at least two
independent ways of egress. One
shall consist of a flight of stairs
from the lowest to the highest floor.
The other shall be approved by the
building commissioner.”
1907
(S. 54) “All tenement houses three
stories in height shall provide one
of the following means of egress: (1)
an interior stairway; (2) an exterior
iron fire-escape and stairs; (3) iron
balconies.”
1915
BOCA was established to provide
a forum for the exchange of
knowledge and ideas about building
safety and construction regulation.
1944
(S. 1803.e) “Every story in a building
shall have at least two remote exits.
(S. 1812) “Fire escapes shall not be
erected to serve as required exits
except from post-code buildings
four stories or less in height and
five thousand square feet or less in
area.”
18
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
1870
1880
1890
1900
1910
1920
1930
1630
In 1630 Boston outlaws
building wooden chimneys
and thatched roofs becoming
the first formal Building Code
in the United States.
On July 8, 1871 the city council of the city of Boston
established and defined the limits with which all
buildings shall conform establishing the Digest of
the Statutes Relating to the Survey and Inspection
of Buildings.
In Massachusetts building codes were done municipality by municipality, and some simply adopted Boston's code as their own
Digest of the Statutes Relating to the Survey and Inspection of Buildings in the City of Boston
Boston
Number of
Single-Stair
Stories Allowed
2
3
4
5
6
State
another unit to reach a stairwell. When
that provision was overridden, the
requirement for retrofitting exterior fire
escapes and fire balconies became
common. As the city grew, older
buildings were often subdivided into
more dwelling units, often requiring
these adjustments, and sometimes
even the addition of a new interior
stairwell or automatic sprinklers.
In 1974, with the adoption of the first
statewide code, single-stair buildings
were heavily curtailed. Research
shows the maximum height allowed
was lowered to two stories, and a
survey of existing structures built
during this time did not find any new
buildings of this type. It wasn’t until
2017, with the adoption of the current
code version, that three-story single-
stair buildings were once again allowed
and began to be built again (albeit in
limited number and size).
Terms
BOCA
IBC
ICBO
ICC
SBCCI
The Building Officials and Code
Administrators International
International Building Code
International Conference of Building
Officials
International Code Council
Southern Building Code Congress
International
1970
(611.1) “Exitways shall not pass
through another living unit.”
(611.3) “Only one exitway shall be
required in multi-family dwellings,
not more than, three stories in height
for not more than six families or not
over two stories and attic in height,
for not more than eight families, nor
more than four families to a floor.”
1974
(609.1) “There shall be two or more
exitways serving every floor area
above and below the grade floor.”
(609.12) “In buildings of type 1-A
or type 1-B construction a single
exitway shall be permitted for
every room, or group of less than
four rooms used for residential
occupancy on multi-family floors.”
1987
BOCA adopts codes requiring
sprinklers in multi-family structures
1990
(807.4) “Exits shall be placed
as remote from each other as
practicable, and shall be arranged
to provide direct access in separate
directions from any point.”
1994
BOCA, SBCCI, and ICBO merged
to form the ICC in order to develop a
singular set of building codes.
1997
(904.7) “An automatic fire
suppression system shall be
provided throughout all R-2
buildings, except buildings having
no more than three dwelling units.”
2000
The first edition of the IBC was
published by the ICC.
2008
(1018.2) “One exit allowed for
maximum height of 2 stories with 4
dwelling units per floor and 50 feet
travel distance equipped throughout
with an automatic sprinkler system.”
(1014.2.1) “Interlocking or scissor
stairs shall be counted as one exit
stairway.”
2010
(1018.2) “One exit allowed up to three
stories, 4 dwelling units per floor and
50 ft travel distance.”
2017
MA Adopts the IBC 2015
2024
MA Adopts the IBC 2021
(current code)
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
19
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
1950
1960
1970
1980
1990
2000
2010
2020
2030
In 1974, the Commonwealth
created a statewide code, which
became the official code.
The 1997 Sixth Edition of the
Massachusetts Building Code was
based on the 1993 edition of BOCA
National Building Code.
The 2008 Seventh Edition
Massachusetts Building Code
Volume was based on the 2003
IBC with significant Massachusetts
modifications.
Statewide Code
BOCA
IBC
SINGLE STAIR TODAY
In the current building code the
height of a single-stair residential
building for multifamily use
(classified as R-2, or non-transient
residential use) is limited to three
stories above grade. The number of
units is further limited to only four
on each floor, with a maximum of 12
units in any building. The building
must also be protected with an
automatic sprinkler system, and its
windows must be of a certain size
and operability to meet emergency
and rescue escape requirements.
While this is what the code allows,
it is not always what gets built.
A survey of recently built single-
stair buildings in Greater Boston
found that few maximize their unit
count, with most having seven or
nine units. In Boston the threshold
for inclusion of income restricted
housing units, (typically 13% of
the total units), kicks in when you
have 10 or more units. Site factors,
including parking, transformers,
and other building services, further
constrain the ground floor of any
given building, and with a maximum
unit count per floor, result in fewer
units overall. While the number of
units is limited, the size of units
are incentivised to grow in order
for developments to gain more
net area. While the code limits the
number of building stories, if units
themselves are multistory (i.e.,
duplex or maisonette), projects can
essentially add another story to the
building while keeping within the
letter of the law. The fourth floor
then does not need access to the
common staircase entirely and is
100% efficient.
While the duplex exception
incentivises larger multistory
units, it’s also only possible in
Massachusetts if the building does
not have an elevator (due to the
units thus not being “accessible”
under 521 CMR7). As a result the
limitation of single-story buildings
to 12 units and three stories actually
results in buildings with four to
nine units, up to four stories, and
with less overall accessibility within
them. The market will always seek
to exploit underlying zoning and
the building code to produce the
maximum return on investment,
which usually means the maximum
residential floor area. As desirable
as this type may be for few more
well-off people to enjoy larger units
in small buildings, it’s a burden to
folks who are presently shut out
of the housing market, and would
greatly benefit from increased
supply and more accessible
homes—an end only possible
through a code that prioritizes
scalable mid-rise housing within
predictable guidelines.
Existing Single-Stair Limits
Axonometric
Floor Plan
L3
L2
L1
Unit 1
Unit 4
Unit 2
Unit 3
60’
(125' Max.)
Occupancy
Max. Units Per Floor
Stories
Max. Exit Access
Travel Distance
+ Equipped with an Automatic
Sprinkler System
+ Equipped with Emergency
Escape and Rescue Openings
Section 1006.3.2 (Single Exit)
R-2
4
≤ 3
125'
20
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
Recently Built Single-Stair Buildings in Greater Boston
47’
86’
59'
52’
49’
41’
70'
74’
58’
45’
61’
70'
34 – 40 Chestnut Ave.
Jamaica Plain, MA
Units
Built
Floor Plate
4
2012
2,545 GSF
471 Somerville Ave.
Somerville, MA
Units
Built
Floor Plate
5
2020
4,810 GSF
191 Condor St.
Boston, MA
Units
Built
Floor Plate
9
2023
3,187 GSF
8 Oakhurst St.
Dorchester, MA
Units
Built
Floor Plate
4
2023
2,480 GSF
110 Savin Ave.
Boston, MA
Units
Built
Floor Plate
9
2019
3,980 GSF
490 Bennington St.
East Boston, MA
Units
Built
Floor Plate
7
2024
2,630 GSF
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
21
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
III. Egress Code Landscape
Across the world, the United States
and Canada are outliers in terms
of their constriction on single-stair
multifamily housing. Only Uganda,
South Africa, and Pakistan also
have height restrictions at or below
three stories; while some countries
(South Korea and Switzerland)
have no limit at all.8 Countries
comparable to the US by climate,
economy, and urban development
generally allow single-stair
buildings of six to nine stories, right
at the threshold to being above
rescue from the ground and thus
becoming “high rise.” The US
limitation arose with our divergence
from the rest of the world in housing
development patterns, but has not
been re-evaluated under recent
changes in both fire-protection
strategies and urban housing
challenges.
Compared to the rest of the world,
North America is unique for two
primary fire safety reasons: light
wood-frame construction and
the historical low density of our
housing stock. Light wood-frame
construction (as opposed to
engineered wood or heavy timber
wood) is rare elsewhere (perhaps
excluding parts of Scandinavia).
The abundance of forests here has
allowed standard stud framing to
be the favored building material
for both single-family homes and
multifamily buildings, and has been
since our cities started growing.
In most other parts of the world
wood was used early on, then
masonry bearing walls with wood
infill framing, and ultimately cast-in-
place or precast concrete became
the favorite residential building
material. Wood being far more
combustible and flammable than
concrete necessitates additional
fire protection measures, both
THE NORTH AMERICAN OUTLIER
Legality of Single-Stair by Number of Stories
1-3 Story Limit
7+ Stories
3-6 Stories
No Data
Sourced from City of Vancouver Report on Point Access Blocks
(Eliason, 2021), and from Second Egress: Building a Code Change
(Speckert, 2024)
2
1
3
4
5
6
7
8
9
10
11
12
Stories
Greater Boston
Average Aerial
Apparatus
Height (75’)
Ground
Ladder
Access
MA (US), South Africa
Canada
Japan, Netherlands,
India, United Arab
Emirates
NYC, Seattle, Honulu,
Kenya, Iran, Scotland,
Hong Kong, Mexico
City, British Columbia
Belgium, Poland,
Normay, Austrailia,
New Zealand
Bangladesh
Jurisdictions
Israel, Portugal, Spain,
Romania
United Kingdom
Uganda, Pakistan
22
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
active and passive. As many
other countries, particularly
those in Europe, became space
constrained, noncombustible
construction and less spatially
draining egress requirements
were natural solutions to allow
development at a density that
could support growth in cities.
In contrast, the US grew most
prominently through suburban
sprawl (its housing mostly in the
form of single-family homes spread
out from each other), and in low to
medium density urban expansion
(which mitigated fire spread
through zoning side yard setbacks
and limited density per acre).
Over the last century,
advancements in fire protection
measures and technologies have
made our buildings much safer,
making the reconsideration of the
two means of egress possible while
maintaining equal or greater safety,
even in light wood-framed buildings.
Similarly, our current affordability
crisis mandates that we think more
creatively about construction cost
and urban typologies, making the
reconsideration of the building code
just as critical as that of the zoning
code. Currently, fire protection
measures in our code range
from active to passive. Passive
measures include limiting building
sizes, heights, and setbacks, but
also modern advancements in
covering wood with nonflammable
materials such as gypsum board
(drywall), and fire-stopping or
smokeproof doors and sealants
to compartmentalize different
units or spaces within a building.
Active building measures, of
which most are modern, range
from automatic door closers,
smoke detectors, smoke control
technologies; and automatic
sprinkler systems; in addition to
fire service advancements such as
Average Number of Fire Deaths per 100,000 Inhabitants (2018-2022)
4.24
3.25
2.40
1.13
1.13
1.11
1.03
1.00
1.00
0.93
0.93
0.82
0.77
0.71
0.66
0.63
0.58
0.52
0.52
0.51
0.51
0.45
0.45
0.42
0.41
0.38
0.34
0.33
0.31
0.25
0.25
0.21
0.20
0.06
0.05
Latvia
Estonia
Cyprus
Japan
Czech Republic
USA
Liechtenstein
Slovakia
Denmark
Iceland
Finland
Norway
Sweden
Taiwan
Greece
South Korea
Kuwait
Portugal
Austria
Belgium
Great Britain
Germany
Saudi Arabia
France
Ireland
New Zealand
Brunei
Slovenia
Spain
Qatar
Israel
Switzerland
Netherlands
UAE
Singapore
≥ 3 Stoires
No Data
0
1
3
2
4
Allow Single-Stair ≤ 3 Stories
From the Center for Fire Statistics
World Fire Statistics Report, No. 29
(excluding countries with less than
$25,000 GDP per captia)
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
23
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
50’ Max.
Dead End
Corridor
(1020.4)
125' Max.
Distance to
Common
Path of Travel
(1006.2.1)
250' Max. Exit
Distance to
Nearest Stair
(1017.2)
Exit
Separation =
(443') > (1/3
of Floor Plate
Diagonal
640' = 214')
(1007.1.1)
Extension Suite
(Single Egress,
limited to 2,000
GSF total)
636’
24’
100'
40'
1-Bed
Unit
50’
125’
87’
65’
39’
107'
65’
75’ Max.
40’ Max.
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
ladder trucks (aerial apparatuses),
fre hydrant proliferation, and
widespread fre safety education in
our schools.
The requirement for two means
of egress arose sometime in the
early to mid-20th century, a passive
measure to ensure redundancy
during a time when building
practices and fre prevention and
attack strategies were inconsistent
and unstandardized. It has
remained on the books due to
its seemingly obvious beneft,
along with respect for previous
fre prevention decisions and an
inclination to leave them in place
unless robust, scientifc, and
consensus driven processes show
alternatives are equally effective.
However, compared to other
countries our own fre record is
not stellar, and the requirement
of two means of egress should
be reconsidered alongside
advancements in fre prevention,
but also in the context of most
countries having deemed mid-rise
buildings of limited foor area with
one stair adequately safe.
Comparing fre loss data across
countries is not precise, but it
does offer a perspective on how
the active and passive measures
infuence fre loss.9 A comparison
of high-income countries shows
that the US is tied for the highest
fre death rate, and that people in
the US are roughly fve times more
likely to die in fres than Swiss
people are, despite Switzerland
allowing single-stair buildings of
unlimited height, and sprinklers
being very rare.10 A large part of
this story has been attributed to
the fact that most Americans live
in single-family homes, which
are almost always unsprinklered,
mostly made of light wood framing,
and with less professional design
Maximum Double-Loaded
Floor Plan (Existing)
Double-Stair
48 Units
41,356 GSF Floor Plate
125’ Max. Common Path
250’ Max. Travel
Maximum Single-Stair
Floor Plan (Proposed)
Single-Stair
4 Units
4,000 GSF FP
75’ Max. Travel
Illegal in MA
Capitol Hill Cohousing
(Seattle, 2016)
Single-Stair
4 Units
3,600 GSF FP
87’ Max. Travel
Legal in MA
Code Maximum
1 Stair (dead end)
8+ Units
5,800 GSF FP
125’ Max. Travel
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
24
and maintenance. In fact, research
estimates that 99% of home fire
deaths occur in buildings without
sprinklers, and the death rate per
fire is more than eight times higher
in buildings without sprinklers.11
In another study it was shown
that, in 95% of fires, the fire does
not spread beyond the room
of origin, further emphasizing
the benefits for sprinklers
and compartmentalization in
construction and downplaying
the impact of a fire occurring in a
stairwell or hallway.12 These facts,
combined with the fact that the
vast majority of fires (91%) occur in
buildings without working sprinkler
systems, weaken the argument that
redundant staircases are our best
defense against fire, even in small
to medium sized buildings. Any
new single-stair construction would
certainly include sprinklers.13
In other countries the requirement
of two stairs does exist, but
generally for much larger or taller
buildings. The logic is predicated
on two assumptions. First, in
the event of a fire and one exit is
blocked, the other one remains
available. And second, that in
that fire event, one stair could be
used for egress, and the other
could be utilized by firefighters for
attack. There are a number of facts
that make these considerations
less necessary for the mid-rise
single-stair buildings this report
focuses on. Firstly, fires and smoke
in hallways or stairs (which are
required to be sprinklered) are
very rare. Fires that originate in
stairwells or corridors from arson
or other sources are so uncommon
that FEMA does not mention
them once in its 2021 report on
building fires, which mines local
fire department reports through the
National Fire Reporting Systems
data (kitchens and bathrooms rank
the highest). Secondly, in the event
one stair is blocked, the separation
of fire attack from resident escape
becomes impossible; and in
practice it’s also rare if at all
possible (based on interviews with
fire service officials, residents use
whichever exit is closest), and
in mid-rise buildings under this
proposal it is more than likely that
most residents will have evacuated
the building far in advance of the
fire department’s arrival in the
first place.
But finally, and most importantly,
the scale of buildings being
proposed are much smaller than
those possible with two stairs,
meaning the amount of people
exiting per stair might be five
times less than in a typical podium
building, and at most equal to
the amount of people currently
permitted to exit through a
single exit in a dead-end corridor
condition. Under current codes,
the maximum building length of
a double-loaded podium building
is more than 630 feet. In such a
building any given resident could
have to travel as far as 250 feet to a
protected exit stair (the maximum
travel distance to the nearest stair).
For residents in units at the ends,
who have only one exit option
because of the dead-end corridor,
the maximum travel distance can
be as great as 125 feet, and the
number of units with access to only
one stair is theoretically unlimited.
In the single-stair building being
proposed in this report, the
maximum number of units, the
maximum travel distance, and the
maximum floor plate size would be
limited to far less than is currently
permitted for a two-stair building.
The result is that the number of
people exiting per stair is far less,
and the length of distance to travel
from a unit through the hallway to a
protected stair could be less than a
third of that in a two-stair building
and at most, half as far.
While the status quo double-
loaded building maintains two
choices for egress, market logics
push for distances far greater
than would be possible under
mid-rise point access blocks.
Shortening this distance, a boon
for egress, also benefits residents
on a daily basis; offering more
social encounters, less distance
carrying groceries, and a shorter
route for less able-bodied people.
These passive measures of
reduction in size, combined with
existing requirements for fire-
rated walls and sprinklers should
more than compensate for the
lack of redundancy in exit access.
Additionally, when considering that
one could build today a building
of up to six stories, with the dead
end of it having only one exit and
five to ten units using that exit, this
report is actually proposing raising
fire safety standards by limiting the
area and units of a PAB—which,
combined on a lot with fire wall
separation, offers greater safety
and compartmentalization than
found in most double-loaded
buildings.
A CHANGING LANDSCAPE
While most states dictate the IBC
limit on single-stair buildings (three
stories), there are outliers and a
momentum of change across North
America. For many years both
New York City and Seattle have
allowed (with some conditions and
caveats) up to six stories of single-
stair multifamily housing, and more
recently Honolulu re-legalized them
to follow the Seattle model code. In
addition, successful legislation in
California, Oregon, and Washington
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
25
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
state will make mid-rise single-
stair buildings legal in either 2025
or 2026. Nine additional states
have ongoing efforts to study
and legalize these buildings. So
do the Canadian provinces of
Ontario and British Columbia, with
guidelines for performance-based
code compliance under review
within the City of Toronto. Finally, a
pending proposal to liberalize the
use of PABs is being considered
by the International Code Council
(ICC), the organization that writes
and publishes the IBC. While this
movement, which began in earnest
perhaps five years ago, is gaining
momentum, it builds upon older
studies such as a 1984 Canadian
report entitled “Fire Safety and the
Design of Apartments, a report
to the Canada Mortgage and
Housing Corporation”. It includes
recommendations for assessing
the National Building Code of
Canada to allow up to eight stories
of single-stair housing. The report
references the same urban strains,
both economic and spatial, that our
cities struggle with today, and the
inflexibility of their building code to
provide relief. Specifically called out
is an analysis between European
and Canadian building layouts and
fire safety records, which shows
Europe far exceeds Canada in fire
safety, even while offering more
flexibility in European apartment
layouts.
Today, the topic of single-stair
housing has made headlines in
multiple design competitions,
articles, videos, panels,
presentations, and podcasts (many
of which are included at the end
of this report for further reading).14
Much of the push has been led by
housing activists, policymakers,
architects, urban planners, and
urbanists. The building code,
which has long been the domain
of trade groups and regulators, is
starting to be understood as an
equally important regulatory tool
as zoning; to be effective, both
require constant dialogue between
those who work under them
and those who write them. The
American Institute of Architects, in
its statement about building codes,
says, “As a group, architects may
be the most significantly affected
by, and the most significant
users of, the codes.” Yet, among
the 109 members of the ICC’s
Industry Advisory Committee,
which writes the International
Building Code most states adopt,
two are architects. Of the 16
members of the Massachusetts
Board of Building Regulations and
Standards, which adopts the model
building code for the state, just one
is an architect. While architects are
only part of the missing picture,
this report contends that the lack
of architectural engagement in
lobbying for the public’s best
interests must be reversed, and
code councils would do well to hear
arguments from those working
directly in areas most in need of
creative spatial and typological
solutions.
Code Change Landscape in the US & Canada
Courtesy of the Single Stair Tracker from
The Center for Building in North America
Currently Legal
New York City
Seattle (1977, modified)
Honolulu (2012, re-
legalized)
British Columbia (2024)
Pending but Accepted15
California
Oregon
Washington State
In Progress States/Cities
National
Canada (NBC Proposal)
US (ICC Proposal)
States/Provinces
Colorado
Connecticut
Minnesota
New York
Ontario (Canada)
Pennsylvania
Rhode Island
Tennessee
Virginia
Cities
Austin
Nashville
New York City (expanding
floor plate size)
Toronto (Canada)
26
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
Nashville
Austin
Honolulu
Seattle
Toronto
NYC
Currently Legal
Reforms
Underway
(State/Province)
(City)
3 Story Limit
2 Story Limit
THE PROPOSAL
The goal of this proposal is to enable
more diverse housing typologies
that fit into existing urban form while
not compromising the safety of
residents. Based upon our research
we recommend that the following
provisions in the table below be
followed for any single-stair multifamily
building.
This recommendation raises the
height currently allowed by three
stories, doubling the number of units
possible in a PAB from 12 to 24. It
does not increase the maximum units
per floor, or any other fire protection
feature currently applied to single-
stair buildings. Similarly, the same
occupancy requirements, non-high-rise
characteristics, and shaft or enclosure
fire-wall ratings would still apply. PABs
of up to six stories and up to 24 units
offer more favorable potential financial
returns for small lots. Those lots then
can have more units close to transit
and other neighborhood amenities.
And those units can be larger, and
have more access to natural light
Proposed Requirements
• 4 maximum units per floor
• 6 stories maximum (non-high rise)
• 4,000 GSF maximum floor plate
• 75' maximum exit access travel
distance
• 20' maximum corridor length
• 45-minute minimum rated unit
entry doors
Additional measures
(if not already required)
• Equipped with a NFPA 13 sprinkler
system
• Two-hour rated exit stair
(smokeproof enclosure)
• Equipped with emergency escape
and rescue openings
• Buildings can be mixed-use, but
other occupancies cannot be above
the ground floor
Optional Measures
• Exit stair discharge requirements
such as mandating it directly exit
to a public way and cannot be
through another occupancy or a
residential lobby
• Stair smoke control features such as
pressurization, stairwell emergency
smoke ventilation systems, or
exterior stairwells
• Even higher unit entry door rating
requirements
• Noncombustible construction type
limitations
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
27
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
< High Rise
L6
L5
L4
L3
L2
L1
<75’
20’ Max.
Dead End
Unit 1
Unit 4
Unit 2
Unit 3
4,000 GSF Max.
Floor Plate
and air than units in typical double-
loaded corridor buildings. In terms
of fire safety, the six story maximum
follows the mid-rise logic adopted by
other domestic municipalities and
by most other comparable countries.
This proposal limits the number of
occupants in possible danger and the
potential fire spread by limiting the size
of buildings and floor plates, while the
maximum travel distance shortens
the time it takes to exit or be rescued.
Upgrading unit entry door fire ratings
from 20-minute (typical in a 1 hour
rated corridor) to 45-minute aids in the
prevention of any unit fire spreading
to the corridor. Existing provisions for
sprinklers, exit enclosure ratings, and
smokeproof construction ensure the
building would match or more likely
exceed the fire protection design of any
six-story building built today.
Compared to a traditional double-
loaded podium building this proposal
calls for a massive reduction in floor
plate size. Each floor plate on such a
building could be as much as 100,000
GSF depending on construction
type, compared to just 4,000 GSF
for buildings under this proposal.
The maximum corridor length of 40
feet would also be 14 times shorter
than the longest corridor in a double-
loaded building today. The building
would be required to not exceed the
high-rise code threshold, ensuring
code exceptions such as the duplex
or mezzanine exploits would not
overburden the height.
As a part of future efforts, potential
additional protections to be considered
are: smoke control features such as
pressurization and stairwell emergency
smoke ventilation systems, even higher
unit entry door rating requirements,
and noncombustible construction type
limitations.
Finally, this report does not recommend
limiting mixed uses (just that the stair
cannot serve or exit through those
uses), limiting the number of PABs
on a single parcel (as Seattle’s code
does), or mandating window rescue
as a strategy, since these would limit
windows on a building to only facades
facing a public street, and negatively
impact the urban design benefits
provided by PABs.
This proposal is a call to all those
who work on housing to consider
how the building code in general, but
specifically in relation to two means
of egress, can be adjusted to allow for
more mid-sized multifamily housing.
One path of reform would be to have
the legislature commission its own
report on the issue. This report could
include:
• Comparisons of fire prevention
strategies and outcomes between
successful US single-stair
jurisdictions, and those abroad.
• Conducting a quantitative risk
assessment of different housing
typologies; both single and
dual stair.
• Conducting a cost comparison
between single-stair and double-
loaded developments.
• Defining the exact code proposal
and language to be adopted as part
of the model code amendment cycle.
• A survey of municipal fire service
departments to understand where it
makes sense for this allowance to be
made, and where it does not.
An outcome of the state’s report might
be code language that the regulatory
committee could utilize and set
provisions for its optional adoption
by any city’s inspectional services
department. Ultimately, Massachusetts
lives within the context of a federalist
nation, in which certain standards
make sense to be federally applied and
others not. In this case, Massachusetts
can be a model for other states or
the county as a whole to follow. Our
reputation as “first in the nation” on
many other initiatives positions us to
lead the effort in developing a robust,
scientific, and consensus-based
pathway to legalize mid-rise PABs.
RELATED BUILDING CODE
PROVISIONS WORTH
RECONSIDERATION
In addition to the focus of this report,
egress requirements, the following
related building code limitations are
also worth serious consideration for
revisions: the high rise height limit,
ground floor unit accessibility, and
exterior stair allowance. All three tie
closely into making single-stair housing
better and more efficient, and have
been undervalued for their provision
to enable more numerous and
delightful housing.
28
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
70’*
*(MA) Measured
from Mean Grade
to top of Structure
75’
10’-11’
12’-15’
Raise the High-Rise Limit to 75'՛
Massachusetts, in its amended
adoption of the IBC, limits high-rise
buildings to 70' instead of 75' as is
allowed in most states and under the
model code. As a result, developers
prefer buildings of 69' – 11" or just
under the limit (typically six stories).
Since going over that limit has heavy
cost implications, buildings are either
at six stories or much higher (12+),
in order to justify the added cost.
Raising the high-rise limit to be in
accordance with the IBC limit would
allow developers to add up to two more
floors of housing in many projects
(since, unlike Massachusetts, the
IBC measures the height to the finish
floor level rather than the roof). This
increase follows accepted international
standards, is consistent with most
other states, and would add a much
needed bump of units to the state’s
production goals.
Permit Duplex Ground Floor Units
Under the Massachusetts Architectural
Access Board, ground floor duplex
units (two-level units), are made
impossibly hard to permit due to
elevator requirements, additional
ingress requirements, and
discrepancies in the code; as such
they are few and far between. However,
these two-level units are critical to
expanding the stock of family-sized
units, and making ground floor, street-
facing units successful. Urbanistically,
not every street needs or can support
ground level retail, and residential
units fronting on a street can activate
a building frontage in a much more
successful way than bike rooms,
screened parking, or blank walls.
Successful ground level units need a
spatial buffer from the street, which
can be in the form of vertical separation
through stoops or porches, or having
the units be duplex themselves, which
put living spaces on the entry level and
sleeping spaces above. Allowing these
units will not sacrifice overall residential
accessibility, and should be a priority
for a state that needs more diverse
housing types and in an economic
climate where retail is rare and where
we need more successful examples of
urban infill housing frontage.
Allow Exterior Egress Stairs
In Greater Boston fire and building
departments generally disallow the
use of exterior egress stairs. However,
exterior stairs are very common in
other countries, including other cold
and humid climates similar to New
England, such as Japan and Northern
Europe. They are also more common
in single-stair buildings, such as those
built under the Seattle code, because
they offer a host of benefits.
Exterior stairwells, being adequately
fire separated from the building
and appropriately covered from the
elements, can be just as safe or more
safe than an interior protected stair,
having less chance to be burdened
by smoke accumulation. The stair has
added benefits of reduced construction
cost and access to more natural
light and air. While the front door
for most single-family homes fronts
the elements, the entries for most
multifamily dwelling units front a dark
interior hallway. Exterior stairwells
and walkways can provide borrowed
natural light to the back-side of units,
and oftentimes are a most pleasant
atmosphere to arrive home to. Similarly
when stairs are enjoyable spaces they
are more likely to be used, which has
numerous social and health benefits.
These should be considered as an
available option apart from the typical
dark concrete cell we know today.
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
29
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
IV. Point Loaded Potentials
BUILDING MORE MID-RISE
In Greater Boston and beyond we
have been building less mid-scale
housing over time. In Boston,
as a percent of all housing built,
the share of buildings under 50
units has fallen from 90% before
1940 to 35% today. In the last
two decades, of all multifamily
buildings built in Greater Boston,
75% of units were in buildings with
50 or more units, while only 15%
of units were in buildings with 10
to 50 units. A multitude of factors
shapes the trend toward larger
buildings, including increasing
construction complexity, rising
land prices and the need to scale
development, higher inclusionary
housing requirements on mid-scale
buildings, and slower entitlement
approvals processes. Permitting
single-stair housing will not be a
panacea, but it has the potential
to be a surgical salve to increasing
mid-rise housing across the region.
Of all parcels in Greater Boston,
76% (or 161,860 parcels) fall
between 3,000 and 15,000 square
feet in area. This represents the
lower and upper limit of where
PABs are feasible, and stops short
of sites where existing two-stair
development is already happening.
While single-stair buildings can fit
on even smaller parcels or provide
wonderful aggregated designs on
even the largest parcels, this report
contends that the greatest benefit
might be seen on the parcels too
small for podium buildings, but
large enough to host a meaningful
amount of new units; it happens
that these parcels in our region
represent the majority of the
urban fabric.
PABS FOR SMALL PLOTS
Share of Total Housing Production by Building Unit Count
(as a share of all units built per year)
Year Building Built
2-4
5-19
20-49
50+
Number of
Units in
Building
Number of Units in Building
0
10
20
30
40
50
60
70
80
90
100
1939
or Earlier
1940-
1959
1960-
1979
1980-
1999
2000-
2019
2020
or Later
for City of Boston US Census
Bureau, 2022. American
Community Survey 5 Year
Estimates
Total Parcel Count by Area in Greater Boston
0-500
1001-1500
2001-2500
3001-3500
4001-4500
5001-5500
6001-6500
7001-7500
8001-8500
9001-9500
10001-10500
11001-11500
12001-12500
13001-13500
14001-14500
15001-15500
16001-16500
17001-17500
18001-18500
19001-19500
20,000+
Parcel Count
Parcel Size in Square Feet
20,000
15,000
10,000
Podium
Building
Viability
Typical Triple
Decker Range
Mid-Rise Single-Stair Opportunity
5,000
0
30
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
In order to look at sites prime for
development among these 161,860
parcels, our study culled ones that
are further than 0.75 miles from
a rapid transit stop (a 15-minute
walk) and sites that are already
developed (by removing those with
more than a floor-to-area ratio (FAR)
of 0.1). We also removed dedicated
open space, and oddly shaped or
unbuildable parcels. The remaining
parcels count 4,955, totalling
33,528,119 square feet. These are
mostly parking lots; vacant, single-
story retail; or other opportunity
areas that are not at their best and
highest use.
Of these sites our study divided
them into three equal buckets by
size and designed preliminary test
fits of single-stair four to six story
buildings. The smallest designs
include both party-wall designs and
smaller unit types; the next largest
sites are ideal for one single-stair
building with four units per floor;
and the largest of sites can host
multiple single-stair buildings
aggregated together to form
compositions of dozens of units.
Mapping these test fits out, over the
range of available parcels available
in transit-oriented areas, could
conceivably net upwards of 130,000
new homes.
The state has a housing target of
creating 200,000 new homes by
2030. If only a small fraction of
these units were built it would make
a meaningful contribution to that
goal, and would unleash a fresh
mid-rise pattern of city building of
a scale that Greater Boston was
founded on, but in recent memory
has faded away. In the past two
decades the scale of podium
housing built on post-industrial
sites at the edges of Boston’s
traditional neighborhoods has not
kept up with the demand for new
Small to Medium Developable Parcels
N
0
5 miles
Parcel
MBTA Rapid Transit
0.75 mile Radius
Boston
Brookline
Newton
Medford
Malden
Revere
Quincy
Milton
Braintree
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
31
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
units. Further, they have failed
fundamentally to create urban
areas of character and vitality. Mid-
rise point access block housing
has several advantages from an
urban design standpoint. The
buildings typically fit on the smaller
lots of existing urban residential
neighborhoods, and when built as
part of a larger new development,
they create a more walkable
neighborhood and when combined
with larger residential buildings,
provide a wider range of unit types
and levels of affordability. They also
make it easier to provide private
outdoor space to each of the units.
Overall, the effect is more housing
on lots where it’s needed, but also
more robust neighborhoods, both
socially and economically.
Successful housing projects stand
the test of time to be recognized
as models to follow. Yet, almost
every architecturally significant
housing project taught in design
schools today is, for one reason or
another, presently illegal to build
in this state.16 The reasons range
from reasonable (new accessibility
and energy codes), to regressive
(restrictive zoning and egress
codes). This report is a call to
change our building code, but
also a call to action for architects
everywhere to more meaningfully
engage in the rules and regulations
by which our designs are bound.
Architecture and other built
environment design disciplines
have an on-the-ground experience
with the technocratic and site
specific constraints through which
American buildings get funded,
planned, built, occupied, and
maintained. These insights often
contrast against a global design
HOMES WE CAN BE PROUD OF
Parcel Shapes
Extra-Small
3,000 – 4,500 SF
1,665 Parcels*
6,106,461 Total SF
Small
4,500 – 7,500 SF
1,538 Parcels*
8,816,113 Total SF
Medium
7,500 – 15,000 SF
1,680 Parcels*
17,988,213 Total SF
4,800 SF
7,200 SF
15,000 SF
14,500 SF
8,500 SF
3,000 SF
38’-57’
80’-
87’
80’-
107’
114’-
199’
60’-67’
75’-108’
4,500 SF
Most Average Parcels
Small
Extra-Small
Medium
32
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
education and professional context
where things are often done
differently. Care should be taken
to consider more meaningfully
these differences, learn from them,
and educate others. It should also
be a call for policymakers and
planners to learn more about the
rules that constrain the physical
design of housing and how best
those rules should be adjusted with
the times, which would also help
ensure inclusionary zoning and
other affordable housing incentives
are feasible in light of design and
construction limitations. Without
such a cross-pollination, we have
no hope of making meaningfully
better buildings than the current
combination of regulations and
market forces decides to deliver, let
alone crafting a fabric of housing
that is more desirable to live in than
old, tired patterns of car-centric and
exclusive development.
Given the life safety issues at stake,
updates to the building code must
be driven by fact-based technical
information. Typically, this area of
expertise has been the purview
of fire engineers and other safety
experts, although it’s also true that
industry organizations who support
their efforts propose updates and
defend existing code definitions
through the lens of their own
interests.17
The housing crisis in
Massachusetts has introduced
other stakeholders to the
conversation about building codes,
and who has the final say about the
priorities that should be considered.
The MBTA Communities Zoning
Law, which requires communities
served by transit and commuter
rail to amend their zoning to
allow for higher density housing,
has helped to make it clear that
other regulations also need to be
Parcel Test Fits
(4)
(5)
66’
36’
(5)
(6)
55’
69’
77’
43’
(6)
(5)
(4)
91’
49’
104’
62’
60’
60’
180’
(XS) Parcel
3,100 SF Parcel
2,300 SF Floor Plate
+/- 8 Units
(XS) Parcel
4,500 SF Parcel
2,700 SF FP
+/- 15 Units
(S) Parcel
5,200 SF Parcel
3,600 SF FP
+/- 20 Units
(S) Parcel
7,200 SF Parcel
4,000 SF FP
+/- 24 Units
(M) Parcel
8,500 SF Parcel
2,200 + 2,600 SF FP
+/- 27 Units
(M) Parcel
4,500 SF Parcel
4,300 (X3) SF FP
+/- 66 Units
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
33
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
amended if right-sized residential
projects are to be built within a
reasonable walking distance from
transit. It is within this context
that both current and potential
future regulations for single-stair
residential buildings should be
considered.
Importantly, most parcels within
the walkshed of transit are in areas
within cities and towns that were
planned and developed before
the Second World War when
speculative development was
executed at a smaller scale using
repeatable market-tested building
types. An increase in the allowable
height and number of units of
single-stair residential buildings
from three stories and 12 units to
six stories and 24 units will help
unlock these transit-oriented sites,
while resulting in better residential
units that are more conducive to
a wider range of apartment types.
As a result, impacts to housing
production and the relative quality
of the residential units that are
delivered should be as much a
priority when weighing the pros
and cons of building code reform
as the life safety issues that have
dominated the discourse to date.
This is not to say that safety should
not be a central focus, but only that
careful consideration should also
be given to how best to mitigate
risk while also considering social
benefits related to the cost and type
of housing that is possible to build.
This report and its
recommendations comes from a
team of architects, urban designers,
planners, policy wonks, housing
advocates, and researchers.
It comes from folks living and
working in the cities and towns
most in need of new housing and
frustrated by what they see as
artificial limits on the shape, scale,
and cost of buildings possible to
meet the needs of our communities.
As we developed this report, fire
chiefs, housing advocates, and
others have been and continue
debating this issue. Both across our
Commonwealth and country and
among our neighbors to the North
in Canada, transparent, diverse,
and fact-based conversations
about the form and quality of
housing should continue to be
pursued. The language of the
building code impacts everyone’s
lives, and its provisions should not
be decided unilaterally by a limited
set of perspectives of those with
expertise in this arcane subject.
All Massachusettsans should
have a say in how to achieve the
appropriate degree of safety in our
buildings while also allowing for
housing that meets other social
needs. If the buildings we want
to have are not possible to build
today we shouldn’t settle for less;
we should instead keep working
to design solutions that enable
housing we all want to live in that
is safe but also affordable, healthy,
and beautiful.
Single-stair egress allows the
implementation of PABs, which
have been the bedrock architectural
typology of mid-rise city-building
for centuries. The benefits to this
type of housing are numerous, and
the downsides of not implementing
it will be felt in the pocketbook
and mindset of millions for
generations—let’s code for the
scale of housing we need, and the
layout of homes we want to live
in, forever.
34
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
35
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
CITATIONS
1 These can include stair
pressurization, additional
mechanical ventilation, fire
access elevator requirements,
more advanced fire alarm
requirements, additional egress
markings, construction type
limitations, elevator lobby
enlargements, and more costly
exterior cladding options.
2 We use this term here and
elsewhere to describe the
combined cities (including
Boston) classified as rapid transit
communities under the MBTA
Communities Act. This includes
Boston, Braintree, Brookline,
Cambridge, Chelsea, Everett,
Malden, Medford, Milton,
Newton, Quincy, Revere, and
Somerville.
3 Also key are various other
regional entitlement thresholds.
Including the Inclusionary
Development Policy (IDP) for the
city of Boston (which requires
13 – 20% of the units to be
affordable), the new stretch
building code (which requires
buildings over 12,000 square
feet to meet Passive House
standards), and the small project
article 80 review process for
the city of Boston (kicks in for
projects over 15,000 gross
square feet, or about 15 units).
4 $200,000 is an average cost
for a CMU-block stairway with
all the necessary features in a
typical US submarket. $500,000
represents the floor area
multiplied by a cost per square
foot of $350, which is common
for new residential construction
in Greater Boston.
5 The Greater Boston Housing
Report Card 2023, Aja Kennedy
et al. The Boston Foundation,
2023.
6 Vermont and Georgia do
not adopt the IBC for critical
chapters on means of egress,
and instead adopt parts of
the National Fire Prevention
Association (NFPA) model
building code, which allows
for single egress multifamily
buildings to be four stories tall
with four units per floor (per
NFPA 101, 20.2.4.6).
7 Section 521 of the Code of
Massachusetts Regulations
(CMR), which is under the
purview of the Architectural
Access Board
8 The practical acceptance in
Switzerland is 75m to 100m.
9 Data collection quality and
validity varies from country to
country. Some countries collect
only data on the worst fires,
while others collect on all fires.
Definitions of terms are also not
fully standardized across these
studies, and less economically
advanced countries have less
quality data to compare.
10 U.S. Experience with Sprinklers,
Tucker McGree. National Fire
Protection Association, April
2024.
11 McGree, 2024.
12 McGree, 2024.
13 NFIRS 5.0, Automatic
Extinguishing System Data
for Nonconfined Multifamily
Residential Building Fires
(2005 – 2007)
14 Two such contests include
Decoding Density from
Urbanarium https://urbanarium.
org/decoding-density#winner-
press-release and Buildner
Architecture Competitions
https://architecturecompetitions.
com/pointaccessblock/.
15 Center for Building in North
America
16 To name a few: 59 Dwellings
at Neppert Gardens, the
Barbican, Buchgrindel II,
Byker Regeneration, Full Stop
& Comma Housing, Hardegg,
Jeanne Hachette Complex,
Justus Van Effen Complex,
Kitagata, Nexus World, and
Unité d’Habitation
17 As evidenced in the evolution
of our elevator requirements:
“The American Elevator Explains
Why Housing Costs Have
Skyrocketed,” Stephen Jacob
Smith. The New York Times,
July 8, 2024.
36
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
Terms
Common Path of Travel
The distance one must travel to get
from the furthest point in a room
to the point of access to another
means of egress
Double-Loaded
An architectural floor plan term
that describes units arrayed off
of a single hallway. Also used to
describe parking layouts with a
central aisle, it is the most efficient
way to arrange units in a building
when two staircases are prescribed,
and thus is the de facto method
of mid-rise housing production in
North America. This type is often
called “hotel” housing by the rest
of the world, where two stairs are
only required for transient housing
types. Conversely, single-loaded
refers to units arranged along one
side of the linear circulation hall,
and point-loaded would be when
units are arranged around a nodal
circulation center.
Dwelling Unit
A policy and code classification
for a residential home within a
multifamily building. It can be a
single story or multistory, and can
be through ownership (condo or
cooperative) or through rental
(apartment).
High Rise / Mid-Rise
A code classification often
demarcated as the point at which
fire rescue service ladders from
the ground can no longer reach the
highest occupiable window. This is
defined in the IBC as 75 feet above
grade plane, but in Massachusetts
has been amended to be 70 feet.
Also an urban and architectural
classification for buildings: 1 – 3
stories are Low-Rise, 3 – 7 are Mid-
Rise, and above 7 are High-Rise.
Net / Gross Floor Area
The efficiency of a building is
measured by dividing its net floor
area, or area that is rentable or
salable, by its gross floor area,
or total area of the building.
This efficiency factor is highly
scrutinized during early design
and development stages, and for
residential construction ranges
from 75 – 90%, most typically at
around 80 – 85%, with the higher
the number meaning a more
profitable and “efficient” building.
Point Access Block (PAB)
A single-stair housing category.
Named because rather than loading
off of a corridor (required when two
stairs need to be connected), one
loads from a singular central core
(point). The term refers to single
buildings but also larger complexes
composed of multiple buildings
next to each other separated by
party fire walls.
Podium Building / Five-Over-One
A light wood-frame (combustible
construction) building on top of a
steel or concrete (noncombustible)
building below. Generally the
former is four to six levels, and
is of construction types III, IV, or
V, and composes the housing
element. The latter is generally
one or two levels, is of types I or
II construction, and comprises
parking, retail, lobbies, mechanical
services, back of house rooms, and
sometimes ground floor units.
Maximum Exit Access
The longest allowed distance
one needs to travel from the
furthest point in a room to reach
the point of entering a rated exit
enclosure (stair). Currently 250' in
a sprinklered multifamily building;
75' in this proposal for a single-exit
sprinklered building.
Means of Egress / Escape
Egress generally refers to a rated
exit enclosed stair or hallway that
is an uninterrupted path from entry
until one reaches a public way.
Escape refers to other methods
of getting out of a building in an
emergency, such as through a
window or being rescued, but is not
the designed method of exit during
a fire event.
Boston Indicators Joint Center for Housing Studies of Harvard University Utile
37
Legalizing Mid-Rise Single-Stair Housing in Massachusetts
RESOURCES
About Here. 2022. “The One Rule
Holding Back Housing and Nice
Apartments” (video).
www.youtube.com/
watch?v=iRdwXQb7CfM
Armlovich, Alex. 2024. “Exit Strategy.”
Architectural Record 212 (5): 31 – 33.
www.architecturalrecord.com/
articles/16880-exit-strategy-the-case-
for-single-stair-egress
Chen, Kevin, and Biswadeep Ghosh.
2024. Single Egress Stair Building
Designs: Policy and Technical Options
Report. Jensen Hughes Canada.
www2.gov.bc.ca/assets/gov/farming-
natural-resources-and-industry/
construction-industry/building-codes-
and-standards/reports/report_for_
single_egress_stair_designs.pdf
Eliason, Michael. January 2022.
Unlocking Livable, Resilient,
Decarbonized Housing with Point
Access Blocks. Larch Lab.
www.larchlab.com/wp-content/
uploads/2022/01/Eliason_CoV-Point-
Access-Blocks-report_v1.2.pdf
Gates, Blandford, and Paul Sandori.
1984. Fire Safety and the Design of
Apartments. Canada Mortgage and
Housing Corporation.
assets.cmhc-schl.gc.ca/sf/project/
archive/research/ca1_mh_84f38.pdf
Grabar, Henry. December 2021. “The
Single-Staircase Radicals Have a Good
Point.” Slate.
slate.com/business/2021/12/staircases-
floor-plan-twitterhousing-Apartments.
html
Housing Forward Virginia. 2023. “The
Single-Stair Case: Rethinking Building
Codes to Legalize Affordability -
xChats” (video).
www.youtube.com/
watch?v=r9cp29fBAwg
Jursnik, Sean (ed.). October 2023.
Expanding Colorado Housing Options:
How to Create Safe, Small Apartment
Buildings. SAR+ Architects.
Justus, Andrew. December 2022.
How to Build More Family-Sized
Apartments. Niskanen Center.
www.niskanencenter.org/how-to-build-
morefamily-Sized-apartments
Kemper, Nicolas. March 1, 2022.
“Cancel the Corridor.” New York Review
of Architecture.
nyra.nyc/articles/cancel-the-corridor
Kennedy, Aja, Peter Ciurczak, Luc
Schuster, Penn Loh, Chelsea Gao, and
Johnny Shively. 2023. The Greater
Boston Housing Report Card 2023. The
Boston Foundation.
www.tbf.org/-/media/tbf/reports-and-
covers/2023/gbhrc2023-full-report.pdf
Love, Timothy. 2004. “Double Loaded:
Everyday Architecture and Windows
for Improvement.” Harvard Design
Magazine Fall 2004/Winter 2005,
Number 21.
McGree, Tucker. April 2024. U.S.
Experience with Sprinklers. National
Fire Protection Association.
www.ctif.org/sites/default/
files/2022-08/CTIF_Report27_ESG_0.
pdf
National Fire Incident Reporting
System (website). Federal Emergency
Management Agency.
www.usfa.fema.gov/nfirs/
PUBLIC Architecture. 2023. Single-
Stair Residential Buildings. BC
Housing’s Building Excellence
Research & Education Grants and the
City of Vancouver.
www.bchousing.org/sites/default/
files/media/documents/Single-Stair-
Residential-Buildings-PUBLIC.pdf
Shafaieh, Charles. 2023. “Creative
Corridors.” The State of Housing
Design. Joint Center for Housing
Studies of Harvard University.
Smith, Stephen, and Eduardo
Mendoza. 2024. “Point Access Block
Building Design: Options for Building
More Single-Stair Apartment Buildings
in North America.” Cityscape: A Journal
of Policy Development and Research
26, no. 1 (2024): 431 – 447.
Smith, Stephen. July 8, 2024. “The
American Elevator Explains Why
Housing Costs Have Skyrocketed.” The
New York Times.
www.nytimes.com/2024/07/08/opinion/
elevator-construction-regulation-labor-
immigration.html
Speckert, Conrad. 2022. Second
Egress: Building a Code Change
(website).
https://secondegress.ca
Speckert, Conrad. February 17, 2023.
“The Curse of the Double Egress.”
Urban Progress.
urbanprogressmag.com/article/double-
egress-stairway-exit-double-loaded-
corridors-curse
Wallasch, Karl, and Boris Stock.
September 21, 2009. “Karl Wallasch
and Boris Stock on Germany’s
regulatory approach to single-stair
high-rise buildings.” 2009. Building.
www.building.co.uk/karl-wallasch-and-
boris-stock-on-germanys-regulatory-
approach-to-single-stair-high-rise-
buildings/3149160.article
I. Status Quo Vs. Single Stair
II. Greater Boston Housing History
III. Egress Code Landscape
IV. Point Loaded Potentials
38